background image

Page 16

 

B

RADFORD

 W

HITE

 C

ORP.

6.  With the unit running, verify the supply gas pressure, manifold gas pressure, and CO

2

 according to the 

table below. 

Natural Gas

Propane

Supply Gas 

Pressure

Typical

7” w.c. (1.7kPa)

11” w.c. (2.7kPa)

Range

5” w.c. ≤ (supply pressure ) ≤ 13” w.c.

Manifold Gas Pressure

2.5” w.c. (0.62 kPa)

CO

2

8%

9.2%

 

Table 4.  Supply Gas Pressure

7. After placing the appliance in operation, the 

Burner Safety Shutoff Device must be tested

.  

To test: 

  (a) Close gas shutoff valve with burner operating.

  (b) The flame will go out and blower will continue 

to run for the post purge cycle. One additional 

attempt to light will follow. Ignition will not occur 

as the gas is off. The ignition control will lockout, 

and will have to be reset before the unit will 

operate.

  (c) Open gas shutoff valve. Restart the appliance. 

The ignition sequence will start again and the 

burner will start. The appliance will return to its 

previous mode of operation.

NOTE:

 Sizes 1000–2000 have two ignition controls 

and two ignitors, which work independently of one 

another. If the ignition control for stages 1 and 2 

fails to properly light the main burners for those 

stages, the second ignition control will still be 

active, and will be able to energize stages 3 and 

4. This, of course, will only occur if all other safety 

devices confirm that the unit will run in a safe 

condition.

4.B 

Set Up for High Altitude 

 

 

( >2500 Feet )

 

   Copper Brute ll appliances may be operated at 

high altitude (7700 ft., 2347 m) with a reduction in 

output of approx-imately 10%. At altitudes of less 

than or more than 7700 ft. (2347 m) the appliance will 

perform equally as well, but with differing reductions in 

output. At elevations higher than 7700 ft. (2347 m) the 

reduction in output will exceed 10% and at elevations 

below 7700 ft. (2347 m) it will be less than 10%. High 

altitude adjustment must not be made on appliances 

operating at elevations below 2500 ft. (762 m).

   No orifice changes are required to adjust the 

Copper Brute ll appliances for high altitude. High 

altitude adjustment is accomplished by adjustment of 

the gas valve manifold pressure and the air shutter(s). 

The required instruments used to assist in these 

adjust-ments are a CO

2

 or O

2

 Analyzer and a U-Tube 

Manometer or other device capable of reading a 

pressure of 2.5-3.0 inches w.c. (0.62-0.75 kPa).

   Start the adjustment process by checking the 

CO

2

 in the “as installed” condition. Adjust the air 

shutter(s) so that the CO

2

 is about 8% or the O

2

 is 

about 6.8% for appliances operating on Natural Gas. 

For appliances operating on LP Gas adjust the air 

shutter(s) so that the CO

2

 is about 9.2% or the O

2

 is 

about 6.8%. Appliances with two blowers should be 

adjusted so that the air shutters below each blower are 

open the same amount.

   Once the CO

2

 or O

2

 has been set, the manifold 

pressure may be adjusted. Remove the 1/8 NPT plug 

from the lower side of the gas valve that is to be 

set and install a fitting, hose and manometer. Start 

the appliance and observe the manifold pressure. 

Manifold pressure must be adjusted to 3.0 in. w.c. 

(0.75 kPa) (for high altitude only, standard operating 

pressure is 2.5 in. w.c. (0.62 kPa)). It is adjusted by 

removing the slotted cap on the gas valve and turning 

the adjustment screw (beneath the cap) clockwise to 

increase pressure and replaced after the adjustments 

have been completed and the fitting, hose and 

manometer have been removed and the 1/8" plug has 

been replaced. Repeat this process until all gas valves 

have been set. 

Note:

 The pressure can be set only 

when the appliance is operating and only when the 

particular gas valve being adjusted is energized by a 

call for heat from the staging control.

   After all of the gas valve manifold pressures have 

been set, the CO

2

 or O

2

 must be reset. CO

2

 or O

2

 

will have changed when the manifold pressure was 

adjusted. Open the air shutter(s) to reduce the CO

2

 or 

O

2

 to the values achieved previously.

   The procedure is complete when all gas valves are 

adjusted to a manifold pressure of 3.0 in. w.c. (0.75 

kPa) and the CO

2

 is adjusted to 8.0% for Natural Gas 

appliances or 9.2% for LP appliances. When using an 

O

2

 analyzer, the correct O

2

 is 6.8% for both Natural 

Gas and LP appliances.

 Caution

Should any odor of gas be detected, or if the 

gas burner does not appear to be functioning 

in a normal manner, close main shutoff valve, 

do not shut off switch, and contact your heating 

contractor, gas company, or factory representative.

 

H2380200-

Ambler, PA 19002
Tech. Service (800) 334-3393
Service Parts (800) 538-2020 

www.BradfordWhite.com

Warranty Service (800) 531-2111 

Litho in U.S.A. © Bradford White 1711   Document 1393

200 Lafayette St.
Middleville, MI 49333
Warranty: (800) 531-2111

Содержание Copper Brute ll BWCH

Страница 1: ...utre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne touchez à aucun interrupteur Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez Appelez immédiatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le sservice des incendies L installation et ...

Страница 2: ...ather Shut Down 9 2 D 5 Anti Short Cycle 10 2 D 6 Time Date 10 SECTION 3 Electrical Connections 11 3 A Installation Warnings 11 3 B Line Voltage Connections 11 3 B 1 Main Power 11 3 B 2 Pump Power 11 3 B 3 Boiler Heater Pump 11 3 B 4 Auxiliary Power Output 11 3 C Low Voltage Connections 12 3 C 1 Field Wiring Inputs 12 3 C 1 a Safety Interlocks 12 3 C 1 b BWCH BWCV Heat Demands 12 3 C 1 c Field Inp...

Страница 3: ...affected parts replaced by a qualified service person 1 C In the Event of a Power Failure The Copper Brute ll can not be operated during an electrical power outage If there is an extended power outage with danger from freezing then the Copper Brute ll and all other water systems should be drained completely When draining the boiler turn off main electrical disconnect switch When placing back in se...

Страница 4: ...us Burner Bank 1 Burner Bank 2 Staging on off Blower Speed high low OAT Outdoor Ambient Temperature when connected Pennant Inlet Outlet Temperature System Inlet Outlet Temperature System Supply Return Temperature when connected DHW Temperature when connected Heat Demand Setpoints NOTE The heat demand set point will turn green in color when active Pump Status 2 A 1 Home Screen Status Window The cen...

Страница 5: ...es Will show an Exclamation when there is a message Clicking onto the Message icon will take you to the message itself The USB functionality will show the USB Icon at this location if being used Active Demands Will show icons that indicate the active parameters that are currently in demand Navigation Bar The Navigation Bar is the constant indicator of where you are as you navigate into and out of ...

Страница 6: ...up and commissioning The installer password is 17 When unlocked in the Installer mode the icon will change to OEM Password Setup and parameter changes available only to the factory Walk Away Result The unit will either Lock or stay Un locked if you walk away What it will do is displayed in the bottom right corner The default delay time to lock is 5 minutes of inactivity This time duration can be a...

Страница 7: ...me screens may only allow you to set one or the other while some other screens example pump selection will allow you to select any or all of the options These windows will reflect the allowable ranges that the setting can be adjusted to Shows the current setting of the Parameter NOTE You can always tell exactly where you have navigated to by looking at the icons in the Navigation Bar In this examp...

Страница 8: ...n the input terminal strip Screen 6 CH DHW Quick Start Selection Screen Touching CH1 DHW1 navigates to the CH1 DHW1 Quick Start Screen 2 D 1 a CH1 DHW1 1 Screen 7 CH1 DHW1 Quick Start Screen NOTE CH1 applies to hydronic units BWCH while DHW1 applies to volume water units BWCV Enable Disable This allows CH1 DHW1 to be enabled disabled The default setting is Enabled Set Point This is the temperature...

Страница 9: ...re at which the Copper Brute ll will limit the boiler outlet temperature to the Minimum Water Temperature Minimum Ambient Temperature The outdoor temperature at which the Copper Brute ll will maximize the boiler outlet temperature to the Maximum Water Temperature NOTE Outdoor functionality is applicable to hydronic units only and is explained in Installation Manual Doc 1392 2 D 4 Warm Weather Shut...

Страница 10: ...ent of the following parameters Hour The hour that will be displayed in the upper banner on each screen and the time captured in the date time stamp for lock out conditions displayed on the history screen Minute The minute that will be displayed in the upper banner on each screen and the time captured in the date time stamp for lock out conditions displayed on the history screen Month The month th...

Страница 11: ...power L1 N1 and Ground shall be connected to the three wires supplied This main power circuit is identified by three solid colored wires 10 AWG black L1 white N1 and green Ground Copper Brute ll sizes 1750 2000 main power L1 N1 and Ground is identified by three solid colored wires 10 AWG black L1 white N1 and green Ground The pump circuit is identified by three 12 AWG wires 3 B 2 Pump Power The pu...

Страница 12: ... Field Input 1 controls the Auxiliary Dry Contact If Field Input 1 is open the Auxiliary Dry Contact is open If Field Input 1 is closed the Auxiliary Dry Contact is closed Only dry contacts can be connected to Field Input 1 Field Input 2 Field Input 2 if used is connected across terminals 11 and 12 of the input terminal strip When connected Field Input 2 controls the Auxiliary Power Output If Fiel...

Страница 13: ... this contact when Field Input 1 is closed otherwise this contact remains open Contact ratings are 250VAC 1 5A maximum function The controller automatically detects the presence of this sensor and initiates a call for heat when the DHW temperature drops below the DHW set point by the value of the DHW On Hysteresis DHW Set Point DHW On Hysteresis DHW heat demand The DHW heat demand is satisfied whe...

Страница 14: ...nd on one end of the cable to avoid ground loop issues If more than two Copper Brute ll units are cascaded together daisy chain the wiring from Copper Brute ll to Copper Brute ll keeping the cables as short as possible A system supply sensor must be installed and connected to the lead boiler see System Supply in Section 5 3 1 4 Temperature Sensors The lead boiler will use this system supply sensor...

Страница 15: ...stallation is complete and fully in compliance with the instructions 2 Determine that the appliance and system are filled with water and all air has been bled from both Open all valves 3 Observe all warnings on the Operating Instructions label and turn on gas and electrical power to appliance 4 Switch on the appliance power switch located on the right side of the unit 5 The Copper Brute ll will en...

Страница 16: ...r device capable of reading a pressure of 2 5 3 0 inches w c 0 62 0 75 kPa Start the adjustment process by checking the CO2 in the as installed condition Adjust the air shutter s so that the CO2 is about 8 or the O2 is about 6 8 for appliances operating on Natural Gas For appliances operating on LP Gas adjust the air shutter s so that the CO2 is about 9 2 or the O2 is about 6 8 Appliances with two...

Отзывы: