COPPER BRUTE II (500 - 2000)  USER'S MANUAL

2.C 

Keypad Operations

The “Back” button jumps to the 

previous screen. 

Screen 2.  

    A typical numeric keypad entry screen.

Screen 3.       A Typical selection screen.

To delete the current setting before 

entering in the new value.

The “Enter” button is used to accept 

the new value that was just entered.

This is the indicator that will be shown when 

the correct password has been entered to 

allow the setting to change.

The highlighted button (orange) 

shows which one is selected.  

Some screens may only allow you 

to set one or the other, while some 

other screens (example: pump 

selection) will allow you to select 

any or all of the options.  

These windows will reflect the 

allowable ranges that the setting  

can be adjusted to.       

Shows the current setting 

of the Parameter.

NOTE: You can always tell exactly where you have navigated to by 

looking at the icons in the 

Navigation Bar.

  

In this example you are in    

“Up and Down” arrows are used to 

increment the setting accordingly.

Home/Configure/Central Heat/Central Heat One

As you navigate in, you will find that all screens have either 

a numeric keypad to enter in your customizable parameters OR 

selection buttons to choose the device of your configuration. 

Содержание Copper Brute ll BWCH

Страница 1: ...utre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils Ne touchez à aucun interrupteur Ne pas vous servir des téléphones dansle bâtiment où vous vous trouvez Appelez immédiatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le sservice des incendies L installation et ...

Страница 2: ...ather Shut Down 9 2 D 5 Anti Short Cycle 10 2 D 6 Time Date 10 SECTION 3 Electrical Connections 11 3 A Installation Warnings 11 3 B Line Voltage Connections 11 3 B 1 Main Power 11 3 B 2 Pump Power 11 3 B 3 Boiler Heater Pump 11 3 B 4 Auxiliary Power Output 11 3 C Low Voltage Connections 12 3 C 1 Field Wiring Inputs 12 3 C 1 a Safety Interlocks 12 3 C 1 b BWCH BWCV Heat Demands 12 3 C 1 c Field Inp...

Страница 3: ...affected parts replaced by a qualified service person 1 C In the Event of a Power Failure The Copper Brute ll can not be operated during an electrical power outage If there is an extended power outage with danger from freezing then the Copper Brute ll and all other water systems should be drained completely When draining the boiler turn off main electrical disconnect switch When placing back in se...

Страница 4: ...us Burner Bank 1 Burner Bank 2 Staging on off Blower Speed high low OAT Outdoor Ambient Temperature when connected Pennant Inlet Outlet Temperature System Inlet Outlet Temperature System Supply Return Temperature when connected DHW Temperature when connected Heat Demand Setpoints NOTE The heat demand set point will turn green in color when active Pump Status 2 A 1 Home Screen Status Window The cen...

Страница 5: ...es Will show an Exclamation when there is a message Clicking onto the Message icon will take you to the message itself The USB functionality will show the USB Icon at this location if being used Active Demands Will show icons that indicate the active parameters that are currently in demand Navigation Bar The Navigation Bar is the constant indicator of where you are as you navigate into and out of ...

Страница 6: ...up and commissioning The installer password is 17 When unlocked in the Installer mode the icon will change to OEM Password Setup and parameter changes available only to the factory Walk Away Result The unit will either Lock or stay Un locked if you walk away What it will do is displayed in the bottom right corner The default delay time to lock is 5 minutes of inactivity This time duration can be a...

Страница 7: ...me screens may only allow you to set one or the other while some other screens example pump selection will allow you to select any or all of the options These windows will reflect the allowable ranges that the setting can be adjusted to Shows the current setting of the Parameter NOTE You can always tell exactly where you have navigated to by looking at the icons in the Navigation Bar In this examp...

Страница 8: ...n the input terminal strip Screen 6 CH DHW Quick Start Selection Screen Touching CH1 DHW1 navigates to the CH1 DHW1 Quick Start Screen 2 D 1 a CH1 DHW1 1 Screen 7 CH1 DHW1 Quick Start Screen NOTE CH1 applies to hydronic units BWCH while DHW1 applies to volume water units BWCV Enable Disable This allows CH1 DHW1 to be enabled disabled The default setting is Enabled Set Point This is the temperature...

Страница 9: ...re at which the Copper Brute ll will limit the boiler outlet temperature to the Minimum Water Temperature Minimum Ambient Temperature The outdoor temperature at which the Copper Brute ll will maximize the boiler outlet temperature to the Maximum Water Temperature NOTE Outdoor functionality is applicable to hydronic units only and is explained in Installation Manual Doc 1392 2 D 4 Warm Weather Shut...

Страница 10: ...ent of the following parameters Hour The hour that will be displayed in the upper banner on each screen and the time captured in the date time stamp for lock out conditions displayed on the history screen Minute The minute that will be displayed in the upper banner on each screen and the time captured in the date time stamp for lock out conditions displayed on the history screen Month The month th...

Страница 11: ...power L1 N1 and Ground shall be connected to the three wires supplied This main power circuit is identified by three solid colored wires 10 AWG black L1 white N1 and green Ground Copper Brute ll sizes 1750 2000 main power L1 N1 and Ground is identified by three solid colored wires 10 AWG black L1 white N1 and green Ground The pump circuit is identified by three 12 AWG wires 3 B 2 Pump Power The pu...

Страница 12: ... Field Input 1 controls the Auxiliary Dry Contact If Field Input 1 is open the Auxiliary Dry Contact is open If Field Input 1 is closed the Auxiliary Dry Contact is closed Only dry contacts can be connected to Field Input 1 Field Input 2 Field Input 2 if used is connected across terminals 11 and 12 of the input terminal strip When connected Field Input 2 controls the Auxiliary Power Output If Fiel...

Страница 13: ... this contact when Field Input 1 is closed otherwise this contact remains open Contact ratings are 250VAC 1 5A maximum function The controller automatically detects the presence of this sensor and initiates a call for heat when the DHW temperature drops below the DHW set point by the value of the DHW On Hysteresis DHW Set Point DHW On Hysteresis DHW heat demand The DHW heat demand is satisfied whe...

Страница 14: ...nd on one end of the cable to avoid ground loop issues If more than two Copper Brute ll units are cascaded together daisy chain the wiring from Copper Brute ll to Copper Brute ll keeping the cables as short as possible A system supply sensor must be installed and connected to the lead boiler see System Supply in Section 5 3 1 4 Temperature Sensors The lead boiler will use this system supply sensor...

Страница 15: ...stallation is complete and fully in compliance with the instructions 2 Determine that the appliance and system are filled with water and all air has been bled from both Open all valves 3 Observe all warnings on the Operating Instructions label and turn on gas and electrical power to appliance 4 Switch on the appliance power switch located on the right side of the unit 5 The Copper Brute ll will en...

Страница 16: ...r device capable of reading a pressure of 2 5 3 0 inches w c 0 62 0 75 kPa Start the adjustment process by checking the CO2 in the as installed condition Adjust the air shutter s so that the CO2 is about 8 or the O2 is about 6 8 for appliances operating on Natural Gas For appliances operating on LP Gas adjust the air shutter s so that the CO2 is about 9 2 or the O2 is about 6 8 Appliances with two...

Отзывы: