(c) Open gas shutoff valve. Restart the
appliance. The ignition sequence will
start again and the burner will start. The
appliance will return to its previous mode
of operation.
Caution
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a
normal manner, CLOSE MAIN SHUTOFF VALVE.
Do not shut off switch. Contact your heating
contractor, gas company, or factory representative.
Gas Type
Air Orifice
Gas Orifice
Differential
Differential
Natural
4.0 to 4.5" W.C.
4.0 to 4.5" W.C.
(1.0 to 1.1kPa)
(1.0 to 1.1kPa)
Propane
4.5 to 5.0" W.C.
4.5 to 5.0" W.C.
(1.1
to
1.2kPa)
(1.1 to 1.2kPa)
Note: Long runs of vent or combustion air piping may
reduce the air and gas differential pressures. This
is acceptable, as long as the air and gas pressure
differentials are within 0.1" (0.025kPa) w.c. of each other.
Table 7. Air and Gas Orifice Differentials at Full Fire.
6.3 Shutting Down the Brute Magnum
1.
Switch off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
If freezing is anticipated, drain the Brute
Magnum and be sure to also protect building
piping from freezing.
This step to be performed by a qualified
service person.
6.4 To Restart the Brute Magnum
If drained, follow Section 6.1 in this manual
for proper filling and purging.
1.
Switch off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
WAIT FIVE (5) MINUTES.
4.
Set the aquastat or thermostat to its lowest
setting.
5.
Open all manual gas valves.
6.
Reset all safety switches (pressure switch,
manual reset high limit, etc).
7.
Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8.
Burner will go through a prepurge period and
ignitor warm-up period, followed by ignition.
Section 7
MAINTENANCE
WARNING
Disconnect all power to the appliance before
attempting any service to the appliance. Contact
with electricity can result in severe injury or death.
7.1 System Maintenance
1.
Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2.
If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3.
Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
4.
Keep the appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.
5.
If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water.
6.
Low water cutoffs, if installed, should be
checked every 6 months. Float type low water
cutoffs should be flushed periodically.
7.
Inspect and clean the condensate collection and
disposal system yearly.
8.
When a means is provided to neutralize
condensate, ensure that the condensate is being
neutralized properly.
9.
Inspect flue passages, and clean with brushes/
vacuums, if necessary. Sooting in flue passages
indicates improper combustion. Determine the
cause and correct.
10. Inspect the vent system and air intake system,
and ensure that all joints are sealed properly. If
joints need to be resealed, completely remove
existing sealing material, and clean with alcohol.
Apply new sealing material, and re-assemble.
7.2 Appliance Maintenance and
Component
Description
Only genuine Bradford White replacement parts
should be used.
Caution
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
See Figures 27, 28 and 32 for location of gas
train and control components.
Содержание BRHHH
Страница 2: ...BRADFORD WHITE CORP Page 2...
Страница 20: ...BRADFORD WHITE CORP Page 20 Figure 8 Water Heater Piping One Heater One Tank...
Страница 21: ...Brute Magnum Page 21 Figure 9 Water Heater Piping Multiple Heaters One Tank...
Страница 22: ...BRADFORD WHITE CORP Page 22 Figure 10 Water Heater Piping One Heater Multiple Tanks...
Страница 23: ...Brute Magnum Page 23 Figure 11 Water Heater Piping Multiple Heaters Multiple Tanks...
Страница 30: ...BRADFORD WHITE CORP Page 30 Figure 17 Wiring Diagram Size 1200 Standard and Codes A and F...
Страница 31: ...Brute Magnum Page 31 Figure 18 Wiring Diagram Sizes 1600 2000 and 2400 Standard and Codes A and F...
Страница 32: ...BRADFORD WHITE CORP Page 32 Figure 19 Wiring Diagram Size 1200 Code B...
Страница 33: ...Brute Magnum Page 33 Figure 20 Wiring Diagram Sizes 1600 2000 and 2400 Code B...
Страница 39: ...Brute Magnum Page 39 Figure 27 Gas Trains...
Страница 49: ...Brute Magnum Page 49 Figure 30 Combustion Components...
Страница 50: ...BRADFORD WHITE CORP Page 50 Figure 31 Gas Train Combustion Air Components...
Страница 51: ...Brute Magnum Page 51 Figure 32 Gas Train Components...
Страница 52: ...BRADFORD WHITE CORP Page 52 Figure 33 Electrical Components...
Страница 53: ...Brute Magnum Page 53 Figure 34 Heat Exchanger Water Path Components...
Страница 54: ...BRADFORD WHITE CORP Page 54 Figure 35 Heat Exchanger Water Path Components...
Страница 55: ...Brute Magnum Page 55 Figure 36 Jacket Components...