Figure 3. Combustion Air and Vent Through Side Wall.
*When vent terminal is less than 10 feet (3m) horizontally
from a forced air inlet, the terminal must be at least 3 feet
(0.9m) above the air inlet.
U.S. Installations (see note 1)
Canadian Installations (see note 2)
A=
Clearance above grade, veranda, porch,
12 inches (30 cm)
12 inches (30 cm)
deck, or balcony
B=
Clearance to window or door that may be
4 feet (1.2 m) below or to side of opening;
36 inches (91 cm)
opened
1 foot (30 cm) above opening
C=
Clearance to permanently closed window
See note 4
See note 5
D=
Vertical clearance to ventilated soffit located
above the terminal within a horizontal
See note 4
See note 5
distance of 2 feet (61cm) from the center line
of the terminal
E=
Clearance to unventilated soffit
See note 4
See note 5
F=
Clearance to outside corner
See note 4
See note 5
G=
Clearance to inside corner
See note 4
See note 5
H=
Clearance to each side of center line
3 feet (91 cm) within a height 15 feet above
extended above meter/regulator assembly See note 4
the meter/regulator assembly
I=
Clearance to service regulator vent outlet
See note 4
3 feet (91 cm)
J=
Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to
4 feet (1.2 m) below or to side of opening;
36 inches (91 cm)
any other appliance
1 foot (30 cm) above opening
K=
Clearance to a mechanical air supply inlet
3 feet (91 cm) above if within 10 feet (3 m)
6 feet (1.83 m)
horizontally
Vent termination not allowed in this location
Vent termination not allowed in this location
for category IV appliances. A vent shall not
L=
Clearance above paved sidewalk or paved for category IV appliances. For Category III
terminate directly above a sidewalk or paved
driveway located on public property
appliances, vent must terminate at least 7
driveway that is located between two single
feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings.
For Category III appliances that do not violate
the previous condition, vent must terminate at
least 7 feet (2.13m) above the sidewalk or
driveway.
M=
Clearance under veranda, porch, deck,
See note 4
12 inches (30 cm) (see note 3)
or
balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the
gas
supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
Содержание BRHHH
Страница 2: ...BRADFORD WHITE CORP Page 2...
Страница 20: ...BRADFORD WHITE CORP Page 20 Figure 8 Water Heater Piping One Heater One Tank...
Страница 21: ...Brute Magnum Page 21 Figure 9 Water Heater Piping Multiple Heaters One Tank...
Страница 22: ...BRADFORD WHITE CORP Page 22 Figure 10 Water Heater Piping One Heater Multiple Tanks...
Страница 23: ...Brute Magnum Page 23 Figure 11 Water Heater Piping Multiple Heaters Multiple Tanks...
Страница 30: ...BRADFORD WHITE CORP Page 30 Figure 17 Wiring Diagram Size 1200 Standard and Codes A and F...
Страница 31: ...Brute Magnum Page 31 Figure 18 Wiring Diagram Sizes 1600 2000 and 2400 Standard and Codes A and F...
Страница 32: ...BRADFORD WHITE CORP Page 32 Figure 19 Wiring Diagram Size 1200 Code B...
Страница 33: ...Brute Magnum Page 33 Figure 20 Wiring Diagram Sizes 1600 2000 and 2400 Code B...
Страница 39: ...Brute Magnum Page 39 Figure 27 Gas Trains...
Страница 49: ...Brute Magnum Page 49 Figure 30 Combustion Components...
Страница 50: ...BRADFORD WHITE CORP Page 50 Figure 31 Gas Train Combustion Air Components...
Страница 51: ...Brute Magnum Page 51 Figure 32 Gas Train Components...
Страница 52: ...BRADFORD WHITE CORP Page 52 Figure 33 Electrical Components...
Страница 53: ...Brute Magnum Page 53 Figure 34 Heat Exchanger Water Path Components...
Страница 54: ...BRADFORD WHITE CORP Page 54 Figure 35 Heat Exchanger Water Path Components...
Страница 55: ...Brute Magnum Page 55 Figure 36 Jacket Components...