NOTE: When installing multiple intake/exhaust terminals on the same wall of a building, the nearest intake
terminal must be at least 5 ft (1.5 m) from the nearest exhaust terminal. Spacing requirements are the same for
roof installation.
Venting continued-
Concentric Vent Terminal Installation Procedure
WARNING
Improper installation, adjustment, service, or maintenance can cause property damage, personal injury, or death.
Consult a qualified installer, service agency, or the gas supplier for information or assistance.
This kit must be used only for terminating this water heater.
DO NOT
use this termination kit for any other appliance.
Using this kit on other appliances and/or water heaters can result in property damage, personal injury, or death.
DO NOT
operate this water heater until the installation and assembly of this kit is complete and the piping
completed. Failure to complete installation before operation can result in property damage, personal injury, or death.
Before beginning any installation, be sure the main electrical disconnect switch is in the
OFF
position. Electrical
shock can cause personal injury or death.
DO NOT
operate this water heater with the rain cap removed or recirculation of combustion products may occur.
Water may also collect inside larger combustion-air pipe and flow to the burner assembly. Failure to follow this
warning could result in product damage, or improper operation, personal injury or death.
CAUTION
DO NOT use field-supplied couplings to extend pipes. Airflow restriction will occur, and the water heater
pressure switches may cause intermittent problems.
Vertical Installation (recommended)
Table 4
– Approved IPEX Concentric Terminals
Description
Bradford White
Part Number
IPEX System
(1738 or 636)
IPEX Part Number
2
” Concentric Termination
239-44069-02
636
196005 (PVC), 197040 (CPVC)
2
” Concentric Termination
---
1738
397005
3" Concentric Termination
239-44069-01
636
196006 (PVC), 197009 (CPVC)
3" Concentric Termination
---
1738
397006
4" Concentric Termination
---
636
196021 (PVC), 197021 (CPVC)
4" Concentric Termination
---
1738
397021
1. Become familiar with the concentric vent terminals listed in Table 4. Refer to instructions inside concentric vent kit.
Refer to the previous section on determining the maximum venting distance and pipe diameter required for the
installation.
WARNING
The 100T250 and 100T300 models are NOT approved for 2 in (5.1 cm) diameter vent pipe. Venting
with 2 in (5.1 cm) pipe on these models may result in damage to the water heater or cause an
unsafe condition. DO NOT use 2 in (5.1 cm) vent or air intake pipe on 100T250/300 models.