Venting continued-
Maximum Vent Length
Table 3 - Maximum Vent Length (Combined Maximum Length for Intake and Exhaust)
60T125
60T150
100T150
60T199
100T199
2
” Vent Pipe
Power Direct
Vent
Power Vent
Power Direct
Vent
Power Vent
Power Direct
Vent
Power Vent
Max. Intake
Length
15 ft
(4.5 m)
N/A
15 ft
(4.5 m)
N/A
15 ft
(4.5 m)
N/A
Max. Exhaust
Length
15 ft
(4.5 m)
30 ft
(9.2 m)
15 ft
(4.5 m)
30 ft
(9.2 m)
15 ft
(4.5 m)
30 ft
(9.2 m)
60T125
100T150
60T150
100T199
60T199
100T250
100T300
3
” Vent Pipe
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Max. Intake
Length
60 ft
(18.3 m)
N/A
50 ft
(15.2 m)
N/A
40 ft
(12.2 m)
N/A
30 ft
(9.2 m)
N/A
Max. Exhaust
Length
60 ft
(18.3 m)
120 ft
(36.5 m)
50 ft
(15.2 m)
100 ft
(30.5 m)
40 ft
(12.2 m)
80 ft
(24.3 m)
30 ft
(9.2 m)
60 ft
(18.3 m)
4
” Vent Pipe
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Max. Intake
Length
85 ft
(25.9 m)
N/A
75 ft
(22.8 m)
N/A
65
(19.8 m)
N/A
55
(16.7 m)
N/A
Max. Exhaust
Length
85 ft
(25.9 m)
170 ft
(51.8 m)
75 ft
(22.8 m)
150 ft
(45.7 m)
65
(19.8 m)
130
(39.6 m)
55
(16.7 m)
110
(33.5 m)
60T125
60T150
60T199
100T150
6
” Vent Pipe
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Max. Intake
Length
85
(25.9 m)
N/A
75
(22.8 m)
N/A
65
(19.8 m)
N/A
85
(25.9 m)
N/A
Max. Exhaust
Length
85
(25.9 m)
170 ft
(51.8 m)
75
(22.8 m)
150
(45.7 m)
65
(19.8 m)
130
(39.6 m)
85
(25.9 m)
170
(51.8 m)
100T199
100T250
100T300
6
” Vent Pipe
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Power
Direct Vent
Power
Vent
Max. Intake
Length
75
(22.8 m)
N/A
65
(19.8 m)
N/A
60
(18.3 m)
N/A
Max. Exhaust
Length
75
(22.8 m)
150
(45.7 m)
65
(19.8 m)
130
(39.6 m)
60
(18.3 m)
120
(36.6 m)
Note:
The venting distance shown in the chart above is the combined maximum distance for the intake and exhaust pipe
and elbows. The intake and exhaust vent terminals may be in different locations (i.e., different walls or one wall, one roof)
provided the intake equivalent venting distance does not exceed the exhaust by more than 30 ft
(9.2 m)
.
WARNING
The 100T250 and 100T300 models are not approved for 2 in (5.1 cm) diameter vent pipe. Venting with 2 in (5.1
cm) pipe on these models may result in damage to the water heater or cause an unsafe condition. DO NOT use
2 in (5.1 cm) vent or air intake pipe on 100T250/300 models.