ENGLISH
2
Control unit input terminals, can be of the NA, NC, SB, DB, CI types.
[+,-]
power supply.
[1,2,3,4] inputs 49..56. Negative reference.
[F3]
for Proxinet 36: NO fuse.
[F3]
for Proxinet 76: self-restoring fuse 1,35 A.
[F3]
For Proxinet 192: self-restoring fuse 1,35 A.
3
Control unit output terminals.
[AUX +, -]
power supply available via self-restoring-fuse protected output F5.
[U1]
positive programmable output protected by 100 ohm resitor (ON=13.8 Vdc, OFF=NA).
[U2]
for the Proxinet 192 it is a C-NA relay output, for the others it’s an open collector output which is
negative programmable and protected by a 100 ohm resitor (ON=0 Vdc, OFF=NA).
[U3, U4]
open collector outputs which are negative programmable and protected by 100 ohm resistor (ON=0 Vdc, OFF=NA).
[NO, C, NC] clean-contacts general alarm relay (ony one for the Proxinet 36).
[F5]
for Proxinet 36: NO fuse.
[F5]
for Proxinet 76: self-restoring fuse 1,35 A.
[F5]
for Proxinet 192: self-restoring fuse 1,35 A.
A short circuit with open collector output activated for an extended time may lead to breaking of the protecting
resitor.
4 / 5
[T, +] terminals for connecting the control unit tamper.
[JP3] bridge to activate / deactivate the tamper (position C deactivates the control unit tamper, and position O
activates it).
6
[PE]
grounding terminal.
[L, L] input terminal for PSTN external telephone line.
[T, T] output terminals for PSTN telephone line outgoing to telephone or control unit.
7
[CN2] connector for GSM module.
[F4]
for Proxinet 36: NO fuse.
[F4]
for Proxinet 76: self-restoring fuse 1,35 A.
[F4]
For Proxinet 192: self-restoring fuse 1,35 A.
8
Dip switch 1 serves to switch the control unit from operational to maintenance mode (ON=Maintenance,
OFF= Operational).
Dip Switch 2 serves to restore the factory codes.
Dip Switch 3 is unused.
DipSwitch 4 serves to reprogram the control unit firmware.
9
[P1]
button to relaunch control unit (not required for restoring parameters; does not alter configuration).
10
[CN3] connector for the PXV64/PXV256 voice guide and language card.
11
[CN1] RS-232 socket for connecting to OC (via RS-23w straight male/female cable) or to Ethernet interface.
[F4]
for Proxinet 36: NO fuse.
[F4]
for Proxinet 76: self-restoring fuse 1,35 A.
[F4]
For Proxinet 192: self-restoring fuse 1,35 A.
12
[JP2]
bridge to power Ethernet interface linked up to the CN1 connector (activates the 12 Vdc on connector CN1
(RS-232) in pin 9). A position = enable 12 Vdc; B position = disables 12 Vdc.
13
[F1]
for Proxinet 36: glass T fuse 3,15 A.
[F1]
for Proxinet 76: glass T fuse 3,15 A.
[F1]
For Proxinet 192: glass T fuse 3,5 A.
14
[Vac] terminals to connect to transformer.
15
[CN7] battery connector.
[F2]
for Proxinet 36: self-restoring fuse 1,6 A.
[F2]
for Proxinet 76: self-restoring fuse 2,5 A.
[F2]
For Proxinet 192: self-restoring fuse 3 A.
16 / 17
If installed, the PXSTB is temperature probe that optimises battery recharges.
[PXSTB] connector for PXSTB probe.
[JP1] bridge to activate (PXSTB and bridge not present) or disable (no PXSTB nor bridge present) the PXSTB
probe.
18
[CN5] connector for input expansion in control unit.
[F3]
for Proxinet 36: NO.
[F3]
for Proxinet 76: self-restoring fuse 1,35 A.
[F3]
For Proxinet 192: self-restoring fuse 1,35 A.
19
[+, U5, U6, U7, U8, -]
CN6 connector for open collector outputs which are negative programmable and
protected by 100 ohm resitor ((ON=0 Vdc, OFF=NA).