7
SAMPLE menu selection:
If you want to go to MEASURES menu use UP and DOWN keys and find MEASURES MENU, press ENTER
key, now you can move on MEASURES menu subitems by UP and DOWN keys.
At the end of sub menus ENTER (EXIT) message is available and while reading this message, if you press
ENTER key you can go back to MAIN menu.
In ALARMS MENU you can see LOG HISTORY, log events are recorded with event time and date.
PASSWORD Menu is used for service purposes. This menu requires a three digit password and should be
used only by qualified service personnel..
2.2.1 Main Menu
Main menu items are described below, navigation through them can be performed using up and down
buttons.
Main menu items
Function
STATUS
The status message which shows the UPS status
COMMAND MENU
→
Enter
“go to Command submenu”
MEASURES MENU
→
Enter
“go to Measures submenu”
ALARMS MENU
→
Enter
“go to Alarms submenu”
USER OPTIONS
→
Enter
“go to User Option submenu”
TIME MENU
→
Enter
“go to Time submenu”
CALIBRATION MENU
→
Enter
“go to Calibration submenu”
ADJUST MENU
→
Enter
“go to Adjust submenu”
INFORMATION MENU
→
Enter
“go to Information submenu”
Go to STATUS MENU
2.2.2 COMMAND Menu items
This menu is used to give commands to the UPS or perform tests on it.
Submenu item
Function
1
SOUND : ON/OFF
(is available)
Used for turning on/off alert sound.
If you press ENTER key the option will change, one press ON, one press OFF.
If the OFF option is selected sound alert is turned off but if a new alarm, UPS
changes the option to ON state.
2 ENTER <BYPASS>
If you press ENTER for 3 seconds, the load is transferred to BYPASS
automatically and the submenu item changes to ENTER <INVERTER> this time.
If you press ENTER for 3 seconds, the load is transferred back to Inverter.
3 ENTER B.TEST>405
If you press enter for 3 seconds battery test starts and lasts for 15 seconds.
If battery test fails A6 BATT FAULT message is shown on panel and this
message stays until you press ENTER key for 3 seconds.
The value on at the right shows the battery voltage during battey test.
Starting time of battery test recorded to log event menu if the test is successful
you can see only BATTERY TEST message on log records..
4 ENTER <BOOST>
If you press ENTER key for 3 seconds boost charge starts. The given time for
boost charge is 10 hours. At the end of this time UPS stops the boost charge.
If the boost charge is active this submenu item changes to STOP BOOST>
005H message the 005H shows that boost charge is going on for 5 hours.
If the number is 10 boost charge stops. If you press ENTER key boost charge
stops immediately.
Boost charge starting and boost charge end times are recorded to log event
menu.
If boost is active UPS beeps each 15 seconds