26
VIII. UPS’s REMOTE CONTROL CONNECTION
Following external connections are available at HP-200P series
•
Communication By serial port connection
•
Dry contact (interface board) connection
8.1 Using Serial Port
A standart Serial communication port is installed to all HP-200P series UPS, by using this port user can take
all information about UPS. All measured parameters, alarms can monitor by this port. This port is interactive
and some commands for UPS is available these commands are listed below.
•
Switch to BYPASS
•
Switch to INVERTER
•
SOUND on/off
•
Adjust UPS time and date
•
Start SIMULATION mode
•
Quick BATTERY TEST
•
BATTERY TEST until battery low alarm
•
CANCEL battery test
•
Turn off UPS output voltage immediately (SHUTDOWN)
•
Turn off UPS output voltage after delay (WAITING SHUTDOWN)
•
Turn off UPS output voltage (SHUTDOWN) and turn on UPS output voltage (WAITING RESTART)
•
CANCEL SHUTDOWN
•
RENAME UPS
Special softwares are required to use the serial port. Some of the commands above are special functions.
These can be used only with TMON software.
8.2 Serial port connection cable
RS485 cables connections are as follows:
UPS Side
Panel Side
9 Tx
2 Rx
7 Gnd
5 Gnd
6 Rx
3 Tx
8.3 Remote control/connection with a modem
The UPS connects to a phone line using its RS232 port and a modem. The operator connects to the UPS by
a computer containing TMON program and a modem. By this way a modem can be monitored using a