7.0 DEFAULT SETTINGS – AND WHAT EACH MENU DOES
Page 9 of 11
Default
Default
Un
415
Set L-L system volts
PFC
ON
Selects whether steps are on AUTO-HOLD-ON-OFF
t
1
Set CT ratio :1
CPI
1
Target Cosphi
Pt
1
Set VT ratio :1
St
10S
Switching Time
Ai
NO
Automatic Initialisation?YES/NO
OUt
AUTO
Selects what each output does.
AUTO-Fon-Foff—AL( starts up ventilation fan )
Expert Menus 200 – 600
To get into these please call your
supplier
200
MEASURING
400
CAPACITOR DATABASE
201
415
Sets system Voltage Level Un
( repeat of Un in Menu 100 )
401
75 secs
Set discharge time to prevent
re-energisation on quick switching sequence
202
1
Sets CT ratio:1 (repeat of Menu
100)
402
5 var
(1.max)
Manual entry of kvar values per step
203
1
Set VT ratio:1 (repeat of Menu
100)
403
AUTO
All
steps
Select what each output does
Same as Out setting in 100 menu
204
10%
Tolerance % of Un Voltage Setting
404
0
Step switch counter
Initial value 0 increases with each switching
205
YES
Select L-L or L-N as measurement
voltage
500
ALARMS
206
90º
Select Phase Angle U - I
501
YES
Select if alarm display is cancelled when fault cleared or
not
207
NO
Ai ( Automatic Initialisation) start
502
YES
THD Alarm setting YES = on
NO =off
208
NO
Activate Step kvar Recognition
503
5%
% setting for THD alarm if on
209
AUTO
Frequency setting for low quality
networks
504
NO
Select if steps are switched off if THDU above target level
210
0ºC
Temp setting offset
505
60 secs
Select time delay of THDU alarm
506
NO
Freeze exits if no CT current
300
CONTROL
507
YES
YES=Service alarm operates when max operating hours or
switchings on any step is reached.
301
60%
% value of kvar for step switching.
508
80,000
Set No. of contactor operations for Alarm
302
1.00
Target PF 1
509
9,000
Set No. of operating Hours for Alarm
303
0.95i
Target PF 2
510
NO
Temperature sensor is set to monitor temp and show it in
the LCD Display.
304
NO
Target PF when exporting
511
NO
Select if Digital input is n/c or n/o
305
10 S
Switch Time per step in seconds
512
NO
Temp. Alarms 513/514 ON/OFF
306
2S
Step switch swap over time
513
30ºC
Temp Setting for exit relay nominated as fan control
307
YES
Activation of Step swap over
514
70ºC
Emergency switch off of steps one by one if temp exceeds
target setting – default = 70ºC
308
NO
Stop Automatic kvar step
detection
515
NO
Target Cosphi setting
309
YES
Blocking defective Capacitor Steps
516
YES
YES= Alarm for defective step if no step kvar output after
3 attempts
310
ON
AUTO-OFF-HOLD setting
517
YES
Step power loss alarm
311
1
Selection of switching sequence.
1=Auto.,2=Last in first
out,3=Kombifilter ,4=Progressive
600
ALARM RESETS
312
0
Reactive kvar offset
601
NO
All alarms back to factory default
313
1
Assymetrical Switching
fast in slow out etc.
602
NO
Resets all recorded data of kvar per step+kvar output of
each step
314
NO
Switch off steps if cosphi is
leading. Used for aux.generators
603
NO
Resets Operating Hours to zero
604
NO
Resets Average PF
605
NO
Rests Highest Ambient Temp
606
NO
Reset all alarms
607
NO
Displays software version
608
NO
Gives password