8.0 TROUBLE SHOOTING 

FAULT

POSSIBLE CAUSE

SUGGESTED   REMEDY

No indication in 

the display

No power supply to terminals 

UM1-UM2

Check for voltage in the range 90-550v 50/60hz   on 

these terminals 

Display shows 

U     

ALARM

Power supply is outside voltage 

tolerance setting.

Check the setting entered on menu 201 and 204 

Display shows

I      

LO

Measured Current is below 15mA

Check CT circuit. Are summated CT’s in opposition? Has 

short circuit link been removed? Is CT circuit broken?

Display shows 

wrong value of 

Voltage  or 

Current 

Incorrect CT or VT ratio has been 

submitted

Check settings of VT and CT. Remember the settings 

are :1 so a 1000/5 CT = setting of 200

Display shows 

wrong value of 

Power Factor

Capacitor Step Size has not been 

recognised, or phase angle setting has 

been wrongly entered in 206

Start Ai in the set up menu, Check the setting of phase 

angle in 206 and rectify if necessary 

Power factor does 

not improve after 

stepping steps in. 

Steps won’t 

switch out

CT in wrong position – see notes 1.2 of 

these operating instructions.

Check position of CT ensure it is measuring total 

current including capacitor current and if split core 

make sure the gap is fully closed up.

Display shows 

I  Hi

    

ALARM

Output from CT is too high – above 5 

amps.

Check the CT ratio selected. Change if necessary

Display shows 

PFC   

 

ALARM

Continuous over compensation or 

continuous under compensation 

Check the capacitors and contactors.

Contactor could be welded in. Check that steps are not 

in the FON setting 

( PFC  /Out in menu 100 )

Is the kvar supplied sufficient for the reactive demand? 

If not under compensation will be reported 

Display Shows

Leading 

Cosphi....c

When you know 

there is lagging 

load 

   

Voltage or current connections wrong 

way around.

Phase angle incorrectly entered 

( 206)

Switch off and swap over Um1 and Um2  ( This is better 

than swapping over the CT connections since voltage 

surges form open circuit CT are avoided)

If necessary check settings of 206

Certain steps 

don’t switch in or 

out 

Wrong selection on the OUt menu

Check to see if some steps have been set as FON or 

FOFF ( permanently on or off ) instead of AUTO

Steps are shown 

as defect.,

FLTY

.

Capacitor step faulty or fuse or 

contactor has failed 

Check capacitor current with clamp on power meter 

and compare with rated current are fuses and 

contactor operating correctly? Replace as required.

Steps won’t ever 

switch in,

but there is 

nothing wrong 

with them

Capacitor step sizes are too big.

Provide more steps of lower kvar per step

EXPORT shows in 

the display but 

there is no export.

CT reversed

Swap over Um1 /Um2  to correct.

Alt the Ai feature has caused this to show. Defeat Ai by 

setting 208=NO

Page 10 of 11

Содержание CXPLUSR

Страница 1: ... Page 4 2 1 Lockout time 75 secs 2 2 Measured Values in the Display Scroll through Menu What do the symbols mean Page 5 3 0 THE QUICK START MENU 100 TO SET CT AND VT RATIOS How to get into Setup Menu 100 Page 6 Setting the nominal system Voltage L L Un Setting the CT ratio Ct Setting the VT ratio Pt Selecting Automatic Self Commissioning Ai Selecting AUTO OFF HOLD for all the steps Page 7 Setting ...

Страница 2: ... capacitor current b The ratio of the CT is such that full load current is about 75 of the CT ratio e g for a Max load of 500 amps select a CT ratio of 800 5 not 5000 5 This is because at the lower current ranges C T s are less accurate c Do not use a CT with too low a ratio for the measured load e g If the load is 750 Amps and you use a 500 5 CT the CT will then be saturated and will give inaccur...

Страница 3: ...1 6 Wiring diagram 1 6 1 CXPLUS R Contactor switching Page 3 of 11 ...

Страница 4: ...art menu 2 2 Measured Values in the Display The three larger digits at the top show system 50 hz power factor e g 0 91i lagging p f 0 91 0 98c leading p f 0 98 If you have a known lagging power inductive load then i should be displayed in the LCD If you see c and you are certain the load is lagging switch off and swap over Um1 and Um2 This is better than swapping over a load carrying CT which may ...

Страница 5: ...e is above 5 check the current taken by the capacitors since high THDU can result in harmonic overload of the capacitor steps Harmonic Blocking reactors must then be fitted to limit harmonic overload current 3 5 7 9 11 13 15 17 19 harmonic voltages as of fundamental 0 i cos Top figure Fundamental 50 60hz Cosphi to 2 decimal places Bottom figure Fundamental Cosphi to three decimal places as require...

Страница 6: ...lted to operate when the voltage is 10 from nominal Un setting C T Setting To set the CT ratio key and the first digit starts flashing Assume the CT ratio is 1000 5 which is 200 1 Always set the CT ratio as a multiplication factor to 1 so for the CT ratio 1000 5 we set Ct to 200 The same sequence with and is used for all the other settings Pt Voltage Transformer ratio setting This is only used whe...

Страница 7: ...ontact can be used to start up the ventilation fan If you select AL for one of the exit relays the default switching temperature is 30ºC when this contact will close FOFF This step is permanently off Fixed off FON this step is permanently on Fixed on Default setting is AUTO 4 0 MANUAL SWITCHING 4 1 Sometimes there is no load on the system when the relay is commissioned In order to test everything ...

Страница 8: ...ltage outside tolerance set in menu 204 thi The second ambient temp set in menu 514 has been exceeded Sequential switching off of steps to bring ambient temp down will commence I Lo Measured current below 15mA Check for open circuit or short circuited CT or insufficient load OPH The limit set for operating hours between servicing has been reached Call the service engr I Hi Measured current too hig...

Страница 9: ...ct time delay of THDU alarm 506 NO Freeze exits if no CT current 300 CONTROL 507 YES YES Service alarm operates when max operating hours or switchings on any step is reached 301 60 value of kvar for step switching 508 80 000 Set No of contactor operations for Alarm 302 1 00 Target PF 1 509 9 000 Set No of operating Hours for Alarm 303 0 95i Target PF 2 510 NO Temperature sensor is set to monitor t...

Страница 10: ... above 5 amps Check the CT ratio selected Change if necessary Display shows PFC ALARM Continuous over compensation or continuous under compensation Check the capacitors and contactors Contactor could be welded in Check that steps are not in the FON setting PFC Out in menu 100 Is the kvar supplied sufficient for the reactive demand If not under compensation will be reported Display Shows Leading Co...

Страница 11: ...he exit relays as ventilation fan contact Data Output BSTO software by TTL on back of relay Operating Temperature 20 70ºC Storage 40 85ºC Humidity 0 95 Dew droplets not permitted Over Voltage Category II Pollution Degree 3 DIN VDE 0110 Part 1 IEC 60664 1 Standards Complied with DIN VDE 0110 part 1 IEC 60664 1 1992 VDE 0411 part 1 DIN EN 61010 1 IEC 61010 1 2001 VDE 0843 Part 20 DIN EN 61326 IEC 61...