BPC CXPLUSR Скачать руководство пользователя страница 2

1.0 CONNECTION TO SUPPLY 

1.1 Installation

 must only be carried out by suitably qualified personnel. All local safety regulations must of 

course be followed including IEE wiring regulations 17th edition if installation is in the UK.  The power 

supply to the relay is taken from the phase – phase 50 or 60hz voltage and connected via a fuse 6A max  to 
Um1 and Um2. The CXPLUS accepts any voltage across Um1-Um2 in the range 90-550V 50/60Hz. Voltage 

Transformers for different supply voltages are a thing of the past. Check that the supply voltage is within the 
limits of the relay rated voltage, and the CT has 1A or 5A output, at full load.

1.2 Current Transformer

The current supply to the relay is taken from a current transformer, which can be split core or ring type 
Class 1., with 5VA rating.  The current transformer (CT) must be kept short circuited until connections have 

been securely applied to terminals K-L. The CT is normally mounted on a different phase to L2-L3 for the 
voltage supply. Other connections are possible – see phase offset menu 206. It is essential to ensure:

a)

That the CT is measuring the 

total load of the feeder to be corrected – including the PFC capacitor 

current

b) The ratio of the CT is such that full load current is about 75% of the CT ratio e.g. for a Max load of 

500 amps, select a CT ratio of 800/5 – not 5000/5. This is because at the lower current ranges C T's 

are less accurate.

c) Do not use a CT with too low a ratio for the measured load. e.g. If the load is 750

Amps, and you use a 500/5 CT ., the CT will then be saturated and will give inaccurate results.  
When mounting the CT, ‘P’ should be pointing in the direction of the incoming supply and ‘L’ towards the 

load. S1 on the CT should be connected to ‘K’ on the relay and S2 to ‘L’ on the relay. The output from the CT 
can be 1A or 5A. The Max ratio of the CT must be such that the smallest step of switched capacitance will 

produce a current of not less than 15mA. Reactive – preferably 20mA. 

Example:  
The smallest step size is 25 kvar., at 415v 3ph 50 Hz. What is the highest CT ratio permissible?.

25 kvar at 415v = 34.7 amps. Capacitor will switch at 60% of nominal kvar = 20.8 amps.
Minimum current = 20mA reactive ., so Max CT ratio = 20.8/.02=1040/1 or 5200/5 for a 25 kvar capacitor 

operating at 415v/3ph/50 hz. A 5000/5 would normally be selected as a max ratio 

1.3 Connect the earth tag link

 on the instrument case to earth 

1.4 Connect in accordance with the wiring diagram

 

for contactors or thyristors

      

1.5 Remove any short circuit links from the CT and relay

Page 2 of 11

Содержание CXPLUSR

Страница 1: ... Page 4 2 1 Lockout time 75 secs 2 2 Measured Values in the Display Scroll through Menu What do the symbols mean Page 5 3 0 THE QUICK START MENU 100 TO SET CT AND VT RATIOS How to get into Setup Menu 100 Page 6 Setting the nominal system Voltage L L Un Setting the CT ratio Ct Setting the VT ratio Pt Selecting Automatic Self Commissioning Ai Selecting AUTO OFF HOLD for all the steps Page 7 Setting ...

Страница 2: ... capacitor current b The ratio of the CT is such that full load current is about 75 of the CT ratio e g for a Max load of 500 amps select a CT ratio of 800 5 not 5000 5 This is because at the lower current ranges C T s are less accurate c Do not use a CT with too low a ratio for the measured load e g If the load is 750 Amps and you use a 500 5 CT the CT will then be saturated and will give inaccur...

Страница 3: ...1 6 Wiring diagram 1 6 1 CXPLUS R Contactor switching Page 3 of 11 ...

Страница 4: ...art menu 2 2 Measured Values in the Display The three larger digits at the top show system 50 hz power factor e g 0 91i lagging p f 0 91 0 98c leading p f 0 98 If you have a known lagging power inductive load then i should be displayed in the LCD If you see c and you are certain the load is lagging switch off and swap over Um1 and Um2 This is better than swapping over a load carrying CT which may ...

Страница 5: ...e is above 5 check the current taken by the capacitors since high THDU can result in harmonic overload of the capacitor steps Harmonic Blocking reactors must then be fitted to limit harmonic overload current 3 5 7 9 11 13 15 17 19 harmonic voltages as of fundamental 0 i cos Top figure Fundamental 50 60hz Cosphi to 2 decimal places Bottom figure Fundamental Cosphi to three decimal places as require...

Страница 6: ...lted to operate when the voltage is 10 from nominal Un setting C T Setting To set the CT ratio key and the first digit starts flashing Assume the CT ratio is 1000 5 which is 200 1 Always set the CT ratio as a multiplication factor to 1 so for the CT ratio 1000 5 we set Ct to 200 The same sequence with and is used for all the other settings Pt Voltage Transformer ratio setting This is only used whe...

Страница 7: ...ontact can be used to start up the ventilation fan If you select AL for one of the exit relays the default switching temperature is 30ºC when this contact will close FOFF This step is permanently off Fixed off FON this step is permanently on Fixed on Default setting is AUTO 4 0 MANUAL SWITCHING 4 1 Sometimes there is no load on the system when the relay is commissioned In order to test everything ...

Страница 8: ...ltage outside tolerance set in menu 204 thi The second ambient temp set in menu 514 has been exceeded Sequential switching off of steps to bring ambient temp down will commence I Lo Measured current below 15mA Check for open circuit or short circuited CT or insufficient load OPH The limit set for operating hours between servicing has been reached Call the service engr I Hi Measured current too hig...

Страница 9: ...ct time delay of THDU alarm 506 NO Freeze exits if no CT current 300 CONTROL 507 YES YES Service alarm operates when max operating hours or switchings on any step is reached 301 60 value of kvar for step switching 508 80 000 Set No of contactor operations for Alarm 302 1 00 Target PF 1 509 9 000 Set No of operating Hours for Alarm 303 0 95i Target PF 2 510 NO Temperature sensor is set to monitor t...

Страница 10: ... above 5 amps Check the CT ratio selected Change if necessary Display shows PFC ALARM Continuous over compensation or continuous under compensation Check the capacitors and contactors Contactor could be welded in Check that steps are not in the FON setting PFC Out in menu 100 Is the kvar supplied sufficient for the reactive demand If not under compensation will be reported Display Shows Leading Co...

Страница 11: ...he exit relays as ventilation fan contact Data Output BSTO software by TTL on back of relay Operating Temperature 20 70ºC Storage 40 85ºC Humidity 0 95 Dew droplets not permitted Over Voltage Category II Pollution Degree 3 DIN VDE 0110 Part 1 IEC 60664 1 Standards Complied with DIN VDE 0110 part 1 IEC 60664 1 1992 VDE 0411 part 1 DIN EN 61010 1 IEC 61010 1 2001 VDE 0843 Part 20 DIN EN 61326 IEC 61...

Отзывы: