Inspection/Servicing
|
63
6 720 644 143 (2010/09)
15.2.10 Setting the heating system pressure
B
If the gauge is below 1 bar (100 kPa) (when the
system is cold), top up the system water between 1
and 2 bar (100 kPa and 200 kPa).
B
If there is a pressure drop: check the expansion vessel
and heating system for leaks.
15.2.11 Checking electrical wiring
B
Check electrical wiring for physical damage and
replace faulty leads.
NOTE:
Risk of damaging the appliance.
B
Only top up the heating system when the
appliance is cold.
Pressure gauge reading
1 bar
(100 kPa)
Minimum system pressure (when
cold)
1 - 2 bar
(100 - 200 kPa)
Optimum system pressure
3 bar
(300 kPa)
Maximum system pressure at
highest heating water
temperature: must not be
exceeded (otherwise pressure
relief valve opens).
Table 24