46
en | Alarms and Relay Connections
AutoDome Pipe Mount
F.01U.251.410 | 1.0 | 2011.08
Installation Guide
Bosch Security Systems, Inc.
4.2.1
Configuring a Normally Open Supervised Alarm
1.
Install a 2.2 K end-of-line resistor in the alarm circuit.
2.
Connect the alarm wires to input 1 or 2 (pin 5 or 6) and to
the ground (pin 7) at the AutoDome.
Figure 4.1
N.O.S. - Normally Open Supervised Connections
3.
From the AutoDome main menu, select Alarms
Setup>Inputs Setup, and set the Alarm Input # to N.O.S.
See the table below for contact and condition details.
4.2.2
Configuring a Normally Closed Supervised Alarm
1.
Install a 2.2 K end-of-line resistor in the alarm circuit.
2.
Connect the alarm wires to input 1 or 2 (pin 5 or 6) and to
the ground (pin 7) at the AutoDome.
Figure 4.2
N.C.S. - Normally Closed Supervised Connections
1
Dry Contact
3
Dome Connector
2
Alarm 1 or 2 only (Pin 5 or 6)
4
Ground (Pin 7)
AutoDome Programmed N.O.S.
Contact
Alarm Condition
Open
Normal
Closed
Alarm
Cut or brake
Tamper
2.2K
1
Dry Contact
3
Dome Connector
2
Alarm 1 or 2 only (Pin 5 or 6)
4
Ground (Pin 7)
2.2K