Table 19 SM048 Operating Temperatures and Pressures
Operating Temperatures and Pressures
Cooling
Heating
Model
Entering
Water
Temp. F
Water
Flow
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp.
Rise °F
Air
Temp.
Drop °F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp.
Drop
Air
Temp.
Rise °F
SM048
PART
LOAD
30°
6.0
64–78
248–303
5–6
15–18
12.0
67–82
254–311
3–4
16–19
40°
6.0
109–134
183–224
18–22
19–23
75–91
261–319
6–8
17–21
12.0
105–128
172–210
10–12
20–25
79–96
267–327
4–5
18–23
50°
6.0
118–144
214–261
18–22
19–23
78–90
273–334
8–10
20–24
12.0
113–138
201–245
10–12
20–24
82–95
280–342
5–7
21–26
60°
6.0
122–149
244–298
17–21
18–22
96–117
286–349
9–11
22–27
12.0
117–143
230–281
10–12
19–24
101–123
293–358
6–8
24–29
70°
6.0
126–154
275–336
17–21
18–22
107–131
299–365
11–13
25–30
12.0
121–148
258–316
10–12
19–23
113–138
306–374
7–9
26–32
80°
6.0
130–159
310–378
17–21
17–21
117–143
311–380
12–15
27–33
12.0
132–153
291–356
10–12
18–22
123–151
319–390
8–10
29–35
90°
6.0
134–164
349–426
17–20
17–20
12.0
129–158
328–401
9–12
18–22
100°
6.0
139–170
392–480
16–20
16–20
12.0
133–163
369–451
9–11
17–21
SM048
FULL
LOAD
30°
6.0
71–87
277–339
6–7
15–19
12.0
75–92
284–347
4–5
16–20
40°
6.0
118–144
194–237
21–25
19–23
84–102
291–356
7–9
18–22
12.0
113–138
182–223
12–14
20–24
88–108
299–365
5–6
19–23
50°
6.0
127–155
226–276
21–25
18–22
92–110
305–373
9–11
20–25
12.0
122–149
213–260
12–14
19–24
98–120
313–383
6–7
21–26
60°
6.0
131–160
259–316
21–25
18–22
108–132
320–391
10–13
23–28
12.0
126–154
243–297
12–14
19–23
113–138
328–400
7–9
24–29
70°
6.0
136–166
291–355
20–25
17–21
120–147
334–408
12–15
25–31
12.0
130–159
273–334
12–14
18–22
126–154
342–418
8–10
27–31
80°
6.0
140–171
328–401
20–24
17–20
131–161
348–425
14–17
27–34
12.0
135–165
308–377
11–14
18–22
138–169
356–436
9–11
29–36
90°
6.0
145–177
369–451
20–24
16–20
12.0
139–170
347–424
11–14
17–21
100°
6.0
149–183
415–508
19–24
16–19
12.0
143–175
391–477
11–14
17–21
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown
are meant as a guide only and should not be used to estimate system charge. This chart assumes rated
airflow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in
heating. Heating data at entering fluid temperatures below 50º assumes the use of antifreeze. As a result
of continuing research and development, specifications are subject to change without notice.