14/36
Valve amplifier VT-MSPA2-2X
| Installation
Bosch Rexroth AG, Edition 04.2020, RE 30232-01-B
7.3
INSTALLATION CONDITIONS
▶ When installing the amplifier, strictly adhere to the ambient conditions
specified in data sheet RE 30232-01.
▶ The housing of the VT-MSPA2-2X features protection class IP20. Requirements
that exceed type of protection IP20 have to be ruled out. Avoid contact of the
VT-MSPA2-2X with hydraulic fluids, acids, bases, corrosive agents, salts, metal
vapors, solvents, etc.
7.3.1 Place of installation
Electronics from Bosch Rexroth are intended for installation in control cabinets.
Outdoor installation is not permitted.
7.4
INSTALLING UND CONNECTING THE VT-MSPA2-2X
The dimensions of valve amplifier VT-MSPA2-2X are given in data sheet RE
30232-01. The installation orientation is vertical. Observe the required mounting
distances:
• The distance to covers and walls must be at least 2 cm.
• At ambient temperatures above 50 °C, provide a minimum distance of 1 cm to
the next assembly.
• By snapping the housing of the VT-MSPA2-2X on a conductive and earthed
mounting rail, the earth connection is established with the rear wall of the
control cabinet. This constitutes HF grounding of the VT-MSPA2-2X.
• Do not use any silicone-containing sealants, adhesives or insulating agents.
• Ensure maintenance-friendly installation, i.e. simple access to the connection
lines. Ensure free access to the connection side.
• Lay cables and lines so that they cannot be damaged and no one can trip over
them.
Install the VT-MSPA2-2X as follows on a DIN mounting rail in the control cabinet:
1.
Disconnect the relevant system part from the power supply.
2.
Snap the back panel of the VT-MSPA2-2X carefully into position on the DIN
mounting rail. Mechanical contact points on the rear panel of the VT-MSPA2-2X
ensure firm seating on the DIN mounting rail and the connection of the housing
to the grounding system of the control cabinet.
Fig. 1: Mounting the VT-MSPA2-2X on a DIN mounting rail