RE 30232-01-B, Edition 04.2020, Bosch Rexroth AG
Commissioning |
Valve amplifier VT-MSPA2-2X
23 | 36
The menu structure and operation of the “Expert Mode” corresponds to that of
the “Standard Mode“. The parameters in the “Expert Mode“ can be found in
chapter 8.5.2 „Explanation of menu level “Expert mode““.
8.5
PARAMETER SETTING
During parameter setting the unit remains in operation.
It continues to monitor with the existing parameters until the parameter setting is
completed.
The following has to be taken into account for parameterizing:
First, select the correct valve by means of the rotary coding switch. As soon as
the position of the rotary coding switch is changed, test jack “v“ outputs the valve
number in the form of the corresponding voltage in Volt [0.1 V/valve number].
Valve no. 13, for example, has a voltage of 1.3 V.
As soon as a valve was correctly accepted (by pressing Set > 1 s), the internal
command value is again signaled at test jack “v“.
To have the valve number shown again at test jack “v” for 5 s, press “-“ once.
▶ Press
[Set]
> 1 s in order to switch to the first settable parameter (simple ramp,
1.
Press [Set]
to edit the selected parameter.
2.
Press [+]
or
[-]
to change the set value.
Set values can be checked with the help of a multimeter. Every set value stands
for a voltage output or a percentage value at the connected multimeter. The
assignments are listed in the tables in chapters 8.5.1 and 8.5.2 (output at test
jack).
If, while a parameter is set, no key is pressed for 10 minutes, the amplifier
returns to normal operation without saving the newly set value.
▶
Press [Set]
to exit the editable parameter. This saves the set parameters.
▶ Press
[+]
or
[-]
until the relevant parameter is displayed.
To switch to the “Expert Mode“ you have to be in the “Standard Mode“: Press
[-]
and
[Set]
simultaneously. In the “Expert Mode”, the general parameter
setting procedure corresponds to the menu level “Standard Mode“.
To exit the “Expert Mode“, press
[Set]
(> 1 s).
The device is again in the operation mode.
Press
[Set]
(> 1 s).
The device is again in the operation mode.
Selecting parameters
Setting parameter value
Exiting editable
parameter
Setting other parameters
Completing parameter
setting