ECODRIVE DKC02.1 Drive Controller
Power connection
11-3
DOK-ECODRV-DKC02.1****-PRJ2-EN-P
Selecting the fuse protector Q1 and line contactor K1
The fuse protector must be rated 1.5 times higher than the actual current
at the power connection
I
N
.
Fuse protection can be implemented using:
•
an automatic circuit breaker (power circuit breaker) or
•
a power circuit breaker or
•
safety fuses.
Select the line contactor according to the phase current at the power line
and the rated line voltage.
The rated current of the line contactor must be 1.5 times higher than the
actual phase current at the power line.
For a rated line voltage of 3 x 400 V, 50 Hz, , the line contactors listed in
the selection table are recommended depending on the phase current
I
N
.
The types specified in the selection table are from the Siemens company
and serve as examples.
Recommended fuse protection
Recommended line
contactor
Phase
current
Line
cross
section
(1)
Automatic
circuit
breaker
(tripping char-
acteristic C)
Power circuit breaker
Safety fuse
(class gl)
(for
U
N
= 3 x 400 V, 50
Hz)
I
N
in A
mm
2
Cur-
rent
in A
N
(3)
Siemens
type
Setting
value in
A
N
(3)
Cur-
rent
in A
N
(3)
Siemens
type
Nominal
operating
current
N
(3)
up to
8.7
1,0
10
5
3VU1300
- .ML00
10
12
10
4
3TF40
12
7
up to
11
1,5
16
7
3VU1300
-.MM00
16
19
16
6
3TF41
16
10
up to
15
2,5
20
9
3VU1300
-.MP00
20
24
20
9
3TF42
22
13
up to
21
4,0
32
15
3VU1300
-.MP00
25
30
32
14
3TF43
32
19
(1) Values apply to PVC insulated multi-wire cables in protective pipes and installation ducts with an ambient te m-
perature of 45 °C (in accordance with EN 60204-1/1992)
(2) The current was fixed based on operating mode AC 3 for a line voltage of AC 400 V, 50 Hz.
(3) N = maximum number of connectable drives taking the starting current into consideration. If more drives are
connected than indicated, a fuse protector or line contactor with a higher current rating must be selected.
Fig. 11-5: Selection table for fuse protector Q1 and line contactor K1