22
en | Configuration
Professional Series TriTech AM Motion Detectors
with Anti-mask, LSN
2018.10 | 01 | F.01U.352.414
Reference Manual
Bosch Building Technologies
The Anti-mask Latched parameter within RPS is set to Yes or No. This parameter determines
whether the Anti-mask alarm condition will require a reset.
How to clear an Anti-mask
1.
Remove any foreign objects that might be interfering or causing the detector to be
blocked or masked.
2.
Let the detector stay idle for 7 sec with no movement in the PIR/microwave Doppler
radar field of view.
3.
Walk in front of the detector to initiate a dual alarm.
The anti-mask alarm is cleared from the detector. If
Anti-mask Latched
is set to
Yes
in RPS,
you will have to have to clear the anti-mask alarm at the control panel.