PRAESENSA
Programming options | en
139
Bosch Security Systems B.V.
Underwriters Laboratories Listing Document (ULLD)
2021.12.21 | V0.15b | F.01U.402.882
Call station
On the Action definitions page of the call station, call station and call station extension actions
could be defined.
Topic
Configure /
programming
Feature or option Permitted
in UL2572
(Y/N/
required)
Possible settings
Value
Settings
permitted
in UL2572
Action
definitions
(Configuring /
definition of
buttons.)
Call station
Function:
Press-to-Talk
(PTT)
Yes
Operation
Momentary - finish on
release
Toggle - finish on switch off
Set to
momentary
for ACU/
LOC
Extension
Acknowledge
and/ or reset
Yes
Operation
Type
Ack/reset
Do once
Trouble
Emergency
Trouble and Emergency
Acknowledge
Reset
Ack and Reset
See
*
*
Select an operation, type and Ackn/reset fitting to the intended use For Types Emergency and
Emergency and Trouble, the option Reset aborts active emergency appears with No as the only
option.
This Ack and Reset of the Emergency state and trouble signals is only allowed on the FRP. It is
not allowed on the CSE connected to a CSLx.
6.4.8
Audio processing
Amplifier
On the Audio processing page of the Amplifier, the audio processing parameters of the
selected amplifier outputs can be set.
Call station
On the Audio processing page of the call station, the audio processing parameters of the
selected call station input can be set.