en | Programming options
PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
6
Programming options
PRAESENSA products incorporates field‑programmable software. In order for the products to
comply with the requirements in the Standard for Control Units and Accessoiries for Mass
Notification systems, UL2572, certain programming features or options must be limited to
specific values or not used at all as indicated in chapter
Programming settings, page 132.
6.1
Check/upload device firmware
All (new) PRAESENSA network devices are delivered with firmware. Initial, the network
devices are delivered with factory firmware and need to be upgraded. All devises need to be
upgraded to the latest available online version.
The device firmware is incorporated in the *.zip file.
i
Notice!
Devices should only be upgraded when the system is not in use.
6.2
Ethernet adapter settings
The PRAESENSA system supports redundant network cabling when Rapid Spanning Tree
Protocol (RSTP) is
enabled
.
By default
RSTP is
enabled
because a PRAESENSA system is, for
UL864 and UL2572 compliance, mandatory installed in a redundant network.
IMPORTANT:
When having RSTP
disabled
, and a redundant network installed,
the system will not function
.
See the PRAESENSA installation manual.
i
Notice!
How to set up PRAESENSA in an Ethernet network is outside the scope of this manual. To
prevent network failures in both PRAESENSA and in a Ethernet network where RSTP is not
supported or allowed, contact your local IT representative in case PRAESENSA needs to be
part of the external/building Ethernet network.
6.3
Logon the application
After the (mandatory) software has been installed on the configuration computer, it must
establish a secured data connection with the PRAESENSA system (controller) to be able to
transfer system data to and from the system (controller) and other network devices in the
PRAESENSA system.
i
Notice!
The logon and configuration time‑out is about 10 minutes. Submit your changes before the
time‑out exceeds, otherwise your changes are lost.
1.
An Initial (administrator) setup logon screen appears with the device Hostname and
Device name of the system controller requesting a (New) administrator username and
password.
–
Notice
that the Initial (administrator) setup login screen is only visible at logon the
system for the first time as administrator
or
when the saved configuration file of the
system controller has been erased.
2.
Enter
the (existing) administrator username (minimum
5
and maximum
64
characters)
and (existing) password (minimum
8
and maximum
64
characters):