Wiring distance
Refer to the table to determine the minimum wire gauge for a single sensor system (one
transmitter and one receiver). The distances specified are between the power source and the
last (farthest) unit on the single wire run. For multiple detector configurations, divide the wire
distance in the table by the number of systems in the configuration (1 system = 1 transmitter
and 1 receiver).
Wire Gauge
Maximum wiring distance
ISC-FPB1-W60QS
ISC-FPB1-W120QS
ISC-FPB1-W200QS
AWG
Ø mm 12V
24V
12V
24V
12V
24V
22
0.65
120 m
(393 ft)
1000 m
(3280 ft)
110 m
(360 ft)
1000 m
(3280 ft)
110 m
(360 ft)
980 m
(3215 ft)
19
0.90
230 m
(754 ft)
2100 m
(6889 ft)
220 m
(721 ft)
2000 m
(6561 ft)
210 m
(688 ft)
1900 m
(6233 ft)
16
1.29
430 m
(1410 ft)
3900 m
(12795 ft)
410 m
(1345 ft)
3700 m
(12139 ft)
390 m
(1279 ft)
3500 m
(11482 ft)
Notice!
This table does not include wiring gauge requirements for optional heaters.
Wiring routes
Refer to the graphics below for wiring routes examples. The illustrations depict both one, and
two sets of detector systems on a single wire run.
The graphics below show simple examples of wiring concepts, depicting how to power the
transmitter and receiver pairs, and how to combine alarm outputs. Local regulatory
requirements and technical parameters specific to a connected control panel determine the
exact details of the wiring. Review local regulations and the connected control panels
technical documentation before planning wire routes and connections. Selecting the proper
wire routes and gauges depend on the number of devices, overall distance, and voltage drop
parameters for each individual device.
4.2
4.3
14
en | Wiring
Photobeam 5000
2016.02 | 03 | F.01U.305.910
Installation and Operation Guide
Bosch Security Systems, Inc.
Содержание ISC-FPB1-W120QS
Страница 1: ...Photobeam 5000 ISC FPB1 W60QS ISC FPB1 W120QS ISC FPB1 W200QS en Installation and Operation Guide ...
Страница 2: ......
Страница 26: ......
Страница 27: ......