Troubleshooting
Unit Status LED (Blink Code) Information
Table 7 Status LED Information
Heating and Cooling
Fault
Status LED Code
Fault Condition
NO FAULT
Status LED is OFF
No fault
INVALID CALL
Status LED solid ON
Invalid call, possible thermostat
wiring issue
HIGH PRESSURE SWITCH
1
HPS open, Instant reaction
LOW PRESSURE SWITCH
2
LPS during a demand call (bypassed
for first 120 seconds)
FREEZE COAXIAL SENSOR
3
FZC below temperature limit
(bypassed for first 30 seconds)
CONDENSATE OVERFLOW
4
Sensed overflow (grounded) instant
reaction
BROWNOUT CONDITION
5
Sensed input voltage at or below 18
VAC
FREEZE EVAPORATOR SENSOR
6
FZE below temperature limit
(bypassed for first 30 seconds)
Troubleshooting Heating/Cooling
Indicator
HTG CLG
Behavior
Solution/Action
HEARTBEAT LED
X
X
LED is flashing two times a
second
Normal HPC Operation.
X
X
LED is flashing at a slow
rate, one flash per second
instead of two
HPC application program is not running.
Connect to Bosch EasyStart app to
update or reload application.
X
X
LED is solid ON
Reboot controller. If condition persists,
HPC application program is not running.
Connect to Bosch EasyStart app to
update or reload application.
X
X
LED is OFF all the time
Reboot controller. If condition persists,
contact customer service to replace the
controller.
STATUS LED
X
X
LED is solid ON
Verify thermostat wiring to make sure (R),
(C), (G), (O), (Y1), (Y2), (W1), (W2), and
(H) are properly wired.