Panel Controller
Fault message | en
51
Bosch Sicherheitssysteme GmbH
User Guide
2017.09 | 7.0 | F.01U.258.929
11
Fault message
This chapter contains information about the following points:
–
Calling up fault indication, page 51
–
Trouble message on the panel, page 51
–
Switching off internal buzzer, page 46
–
Resetting malfunction message, page 54
–
Isolating an element, page 55
11.1
Calling up fault indication
Notice!
If a fire alarm is reported, the system automatically switches to alarm indication. To return to
the fault indication, select
Fault
on the status bar. In the event of a fire alarm, the display
automatically switches back to the alarm indication after 30 seconds.
To display the fault messages from the alarm indication or any other menu, select the
following on the status bar:
–
Fault
: A list of all reported fault types and the number of faulty elements are displayed.
–
Status
: A list of all current messages, grouped by message type, is displayed. The number
of elements is also given in each case.
To display the fault messages, select the message category you require — in this case,
Fault.
0
Fire
0
Control
8
Fault
0
Bypass
Status
!
Caution!
If a message does not have to be reset, it is removed from the display as soon as the fault has
been rectified.
Notice!
If individual elements that are combined with other elements in a group are malfunctioning,
the respective element group is displayed first of all. To display the individual elements,
select the element group you require. See also Displaying individual elements of an element
group, page 53.
11.2
Trouble message on the panel
11.2.1
Acknowledging a message
There are two ways to acknowledge messages:
–
Acknowledging all displayed messages: Select
Acknowledge
.
–
Acknowledging an individual message: First select the message and then press
Acknowledge
.
Element groups
Logically addressed logical zones are displayed in a list.
List fields with black background indicate unacknowledged fault messages.
List fields without distinction indicate acknowledged fault messages.