Panel Controller

Diagnostics | en

65

Bosch Sicherheitssysteme GmbH

User Guide

2017.09 | 7.0 | F.01U.258.929

1.

In the start menu, select 

Diagnostics

2.

Network services

3.

Routing table

 

A table with routing information is displayed.

All networked nodes that can be reached via the node currently being operated and that are
recognized within the system network are displayed under 

Node

.

CAN1 to USB1 designate the interfaces on the currently operated panel node. In this example,
it is the node 1 interfaces.
The type of interface on the panel node currently being operated is listed under 

interface

.

The following interfaces can be designated:

CAN 1 interface

CAN 2 interface

Ethernet 1 (IP multicast or UDP tunnel)

Ethernet 2 (IP multicast or UDP tunnel)

Serial Interface

USB 1 interface

The number of nodes that need to be passed in order to reach the listed node is entered
under 

distance

. For nodes that are directly reachable via IP multicast, the value is 1; for nodes

that are connected via other interfaces (e.g. CAN) to nodes reachable via IP multicast, the
value is increased in increments accordingly (e.g. connected via IP mul CAN1/CAN2,
value = 2).
A node number from 1 to 64 can be assigned to panels. All numbers above 240 (241-255) are
assigned dynamically and used, for instance, for an OPC server or a PC with FSP-5000-RPS
software.

14.7.2

Consistency check

Inconsistencies between the network settings configured in FSP-5000-RPS and those set in
the panel controller are displayed under 

Diagnostics

 - 

Network services

 -

Consistency check

.

1.

In the start menu, select 

Diagnostics

2.

Network services

3.

Consistency check

 

Where inconsistencies are identifiable between the network settings saved in the panel
controller and those configured in FSP-5000-RPS, these are indicated. You can use the
arrow key on the display to alternate between displaying 

Problems of active

configuration

 and 

Problems expected after restart

.

Problems of active configuration

The table indicates inconsistencies between the network settings of the panel controller's
active configuration ("

active

") and the settings configured in RPS ("

configured

").

Problems expected after restart

The table indicates inconsistencies between the network settings that have already been
configured on the panel but which do not take effect until restart ("

saved

") and the settings

configured in RPS ("

configured

").

14.7.3

Ethernet ports

To display a table listing the various parameters and the status of the two Ethernet ports:
1.

In the start menu, select 

Diagnostics

2.

Network services

Содержание FPA-1200-MPC-C

Страница 1: ...Panel Controller MPC xxxx C FPA 1200 MPC C en User Guide ...

Страница 2: ......

Страница 3: ... 2 2 Isolate 12 3 3 Diagnostics 13 3 4 Maintenance 14 3 4 1 Walktest 14 3 4 2 Change language 15 3 4 3 Activate Outputs 15 3 4 4 Activate the transmission device 15 3 4 5 Detector removal 15 3 4 6 History Log 15 3 4 7 Change device on V 24 Interface 16 3 5 Configuration 16 3 6 Switching to day or night mode 17 3 7 Further functions 17 3 8 Search Function Element 18 3 9 Reset 18 4 In overview 19 4 ...

Страница 4: ...a Ethernet 36 7 1 IP settings 36 7 2 Ethernet redundancy 37 7 3 Diagnostics 38 8 Remote keypad 39 8 1 Operation and display 39 9 Alarm 40 9 1 Types of alarm 40 9 2 Entry delays 40 9 3 Day and night mode 41 9 4 Alarm message to the panel 42 9 4 1 Optical and acoustic signals 42 9 4 2 Displaying the detector zones in alarm state 42 9 4 3 Sequence of the alarm messages 43 9 4 4 Information about logi...

Страница 5: ...6 12 2 Bypassing and un bypassing elements 56 12 3 Displaying and un bypassing bypassed element groups 57 12 4 Displaying list of all bypassed elements 57 12 4 1 Using the menu 57 12 4 2 Via the status bar 58 12 5 Bypassing Un bypassing buzzer 58 13 Isolate 59 13 1 Menu overview 59 13 2 Isolating and de isolating elements 59 13 3 Displaying list of all isolated elements 59 13 3 1 Using the menu 60...

Страница 6: ...ory log 77 17 1 Selecting filters 77 17 2 Setting filters 77 17 3 Change Filter 78 17 4 Combining several filters 78 17 5 Status bar functions 78 17 6 Printing out data 79 18 Day and night mode 80 18 1 Switching between day and night mode 80 18 2 Showing details 81 18 3 Changing the time for resetting to night mode 81 19 Configuration 83 19 1 Menu overview 83 19 2 Input Output Group Set Up 83 19 2...

Страница 7: ...efinitely 89 20 3 2 Enter the 24 hour master password 90 20 4 Remote Services 90 20 5 Change password 91 20 6 Performing a fire drill 91 20 7 Alarm Counters 92 21 Reset 93 21 1 Menu overview 93 21 2 Resetting elements 93 22 Search Function Element 94 22 1 Menu overview 94 22 2 Searching for function and device description 94 22 3 Search element 94 Index 95 ...

Страница 8: ... operated the panel controller switches to standby mode after 5 minutes and an alarm event occurs after one hour The touch screen backlighting switches off To quit standby mode touch any part of the touch screen To call up the start menu or change the language display see Operating principle page 24 You will find specific topics in the table of contents If you are already practiced in the handling...

Страница 9: ... default language set in the FSP 5000 RPS is displayed again 1 5 Warranty and liability Warranty and liability claims for personal and property damage are excluded if these were caused by one or several of the following causes Use of the FPA 5000 FPA 1200 fire panel contrary to the regulations Improper set up installation start up operation or maintenance Disregarding of the user manual Subsequent...

Страница 10: ...tem is ever sold Notice The personal access code consisting of user ID and password must not be made known to third parties 2 1 Symbols and notes used The various chapters only contain whatever safety information and notes are required for operation of the system Warning notes and operator guidance notes are displayed in the appropriate parts of the panel controller display for your benefit The fo...

Страница 11: ...ouble messages Bypassing isolating and resetting elements Performing a walktest Display diagnostic information about every LSN element Configuration of detectors short texts and detector sensitivity Performing a drill Saving displaying and printing out events Switching the system to day or night mode 2 5 Skills required by personnel Display of event messages on the panel controller must only be pr...

Страница 12: ...stem Annunciator Bypass group More Control element Interface module Show bypassed devices Display of a list of all bypassed elements Un bypassing the bypassed elements Select by number Display of a list of all bypassed elements Search for an element in a list by entering the number Un bypassing or bypassing an element 3 2 2 Isolate Bypass Block Bypass Show blocked devices Select by number Block Gr...

Страница 13: ...panel software version Module status Display hardware diagnostic data for the selected module Only for LSN modules Module status and counters Reset counters Reset the counters that record the frequency with which various events occur Hardware Address cards Additional display for each card slot of the serial number and number of addresses per card Display LED test Test all LED displays on the panel...

Страница 14: ...ration RSTP or dual homing In the case of redundancy via RSTP the RSTP parameters of the RSTP panel local bridge and those of the root bridge are displayed Remote services Information concerning parameters and status of Remote Services Connect the panel manually to the Remote Portal server the panel automatically tries to connect to the server every 15 minutes VAS Information on all connected elec...

Страница 15: ...elements Search for an element in a list by entering the number Sounder Strobe HVAC More Start and terminate activation of the selected elements 3 4 4 Activate the transmission device Activate a selected transmission device Activate transmission device 3 4 5 Detector removal Bypass all sounders and transmission devices for 15 minutes while a detector is being removed Remove detector 3 4 6 History ...

Страница 16: ...Rename walktest bypass and isolate groups Detector sensitivity Change the sensitivity of individual detectors or zones Two selection options are available a default sensitivity and an alternative sensitivity assigned in the FSP 5000 RPS programming software Operator If the same password is used per access level the following options are offered Change universal password The same password can be co...

Страница 17: ...l is configured one of these two options will be offered Entering a master password that is valid indefinitely This password cannot be changed and is available from the relevant Bosch branch on request Entering a master password that is valid for a specified period of time This password is only valid for 24 hours and must first be requested see Master password page 89 After the password has been e...

Страница 18: ... description from the list Go to element Display of a list of all elements that are connected to the system and select an element from this list in order to display more detailed information by logical address Search for an element in a list by entering the logical address allocation by physical address Search for an element in a list by entering the physical address allocation By description Sear...

Страница 19: ... Fault System Fault Signals 0 Bypass Isolate Maintenance Switch to day mode Search Function Element Diagnostics Configuration Further functions Reset 0 0 0 Fire Control Fault Bypass Status 1 1 2 1 3 4 1 Function keys 3 Key switch 2 Alphanumeric keypad 4 LED display 4 1 Operating elements The operating elements include points 1 3 Function keys To select a function press the appropriate membrane key...

Страница 20: ...that is not confirmed by selecting the OK field on the touch screen Alphanumeric keypad Entry of letters special characters and numbers Key switch The key switch has two programmable key positions Depending on the configuration it is possible to switch between day and night operation for example Notice Only give the key to people who have been trained to operate the panel controller and who have k...

Страница 21: ...vice is not activated Signals disabled Yellow x Signaling devices are not activated Operation Green x Panel is operational Green x Panel controller is booting and is not yet operational Green x Power supply fault Fault Yellow x Fault message present Fault System Yellow x Main processor is malfunctioning Fault Transmission Device Yellow x Transmission device is malfunctioning Fault Signals Yellow x...

Страница 22: ...his icon is only displayed on the remote keypad if no connection has yet been established Panel 4 1 I Level 4 logged in The network address and the access authorization of the operator who has logged in 4 are displayed This symbol is displayed if a ground fault occurs in the system The names of the selected menus are also listed Having the menu path displayed will assist your orientation For reaso...

Страница 23: ...n overview of the type and nature of all message types received by the panel Status Display of a list of the various message and status types and the number of elements in the respective state To display the individual elements touch the relevant field with your finger The Control and Trouble status fields are identified by the letters B and or C B means that controllers for type B fire safety equ...

Страница 24: ...s authorization you can use only particular functions In the following cases you will be asked to enter a password You are not logged in and want to select a function for which a password is required You are already logged in but a higher access authorization is required for the function you have selected 5 1 1 Logging in To log in to the panel controller 1 Press the key key The login window is di...

Страница 25: ...tion is logged on you will be asked to enter your user ID and password Access authorizations are assigned for access levels two to four Only a few functions can be used on access level one while all functions can be used on access level four To check the access authorization of the person who is logged in press the key key after logging in The relevant access authorization is displayed 5 3 Calling...

Страница 26: ... Function fields 3 Search mask In many menus elements are displayed in lists The elements are sorted either by description or address Up to three different sorting criteria can be offered By description sorted by description in alphabetical order address allocation also given By number sorted in ascending order by number logical or physical address description also given By number no description s...

Страница 27: ... list An arrow is only displayed if scrolling is possible Rapid scrolling To scroll quickly through a list press the double arrow key on the membrane keypad or on the status bar of the display A scrollbar appears on the status bar Gently touch the horizontal line to jump to a particular place To jump to the beginning of a list touch To jump to the end of a list touch 5 7 2 Various states of list f...

Страница 28: ...on To select elements functions from a list touch one or more list fields on the touch screen with your finger In order to scroll forward or backward select the up arrow back or the down arrow forward To scroll quickly using the scrollbar select the double arrow key on the membrane keypad The activated list field is marked To search for and display a particular element see Search Function Element ...

Страница 29: ...ns how to enter text Enter the initial letter and if necessary other letters The name is automatically completed once it has been uniquely recognized The list field of the element you are searching for is displayed at the beginning of the list Notice The more accurately the description of an element in the FSP 5000 RPS programming software is entered the more successful the search by name will be ...

Страница 30: ...umber and By number no description shown lists In the search screen for the By description list both letters and numbers can be entered Example Entering the letter K and the number 4 in the search screen of a list 1 Press the key A sequence of letters and numbers is displayed on the info bar 2 Keep pressing the key until the required letter in this case K is marked on the info bar K is displayed o...

Страница 31: ...hanging language display page 70 5 10 1 Entering key combination 1 Select the home key immediately followed by the 1 on the alphanumeric keypad A query window will appear 2 Select OK to confirm the entry or Cancel to cancel the operation A list of the existing languages is displayed 3 Select the language you require The displays will now be shown in the selected language Notice After the system st...

Страница 32: ...2017 09 7 0 F 01U 258 929 User Guide Bosch Sicherheitssysteme GmbH Physical Elements Modules Loop Element Numbers 5 1 4 Logical Elements Zone Element Numbers 3 4 Examples Element with physical addressing 5 1 4 Element with logical addressing 3 4 ...

Страница 33: ...l that is operated by another panel Bypass Isolate Switch to Walktest Change configuration You can reset elements and read out the history log 6 1 Icons on the display The following icons are displayed in the standby display info bar list field of a networked panel depending on the type of connection Further explanations of the icons can be found in Establishing a remote connection with a networke...

Страница 34: ...e is a remote connection between panel A and a networked panel B The networked panel B is operated from panel A and is blocked for operation The following icon is displayed in the info bar of panel B If in this example a panel B also establishes a remote connection in this case with a panel C the following icon is displayed The networked panel B with which panel A has already established a remote ...

Страница 35: ... is already being operated from a panel A If the connection is restricted a panel can only be operated in read only mode All dialogs can be accessed in read only mode and the history log can be read out This icon is displayed if there is a restricted connection with a networked panel 1 In order to convert a restricted connection into an isolating connection select the Network key 2 Respond to the ...

Страница 36: ...way multicast address and port number are indicated When you commission the panel controller for the first time all values are set to 0 6 Select Default settings to overwrite these values with the default settings saved in the panel controller recommended The IP address in this case corresponds to the stored default IP address the last number of which matches the rotary switch number RSN that was ...

Страница 37: ...es may only be made by trained specialist personnel Competent knowledge of networking and protocols is essential Permission level 4 is required for changes to the RSTP parameters of a previously configured panel To modify the parameters for redundancy via RSTP or to configure these for the first time 1 Select RSTP as the redundancy type 2 Select Set parameters The values for bridge priority hello ...

Страница 38: ...status of the two Ethernet interfaces available at the panel controller Send ping command Sending of a ping command to a specific IP address to check the availability of other nodes in the network Consistency check The check performed determines whether the Ethernet configuration from FSP 5000 RPS corresponds to the configuration entered at the panel controller In the event of discrepancies a faul...

Страница 39: ...rization 1 is logged in If an operator with access authorization 1 is logged in no LEDs are activated and no messages displayed If no operator is logged in only the standby screen is displayed Notice It is possible to specify in the FSP 5000 RPS programming software that messages are to be displayed on the remote keypad even if no operator is logged in In this case the operation of all functions i...

Страница 40: ...e panel controller a distinction is made between the following types of alarm Fire Heat heat Smoke Water Supervisory Depending on the configuration external transmission devices e g fire department notification appliances e g sirens and or strobes and fire protection systems e g sprinkler systems fire doors are activated Notice If an alarm delay is set for the detector triggering the alarm the ala...

Страница 41: ...isplayed on the system as a pre alarm The transmission device to the fire department is not activated The detector generating the alarm is reset after the first signal The pre alarm becomes the main alarm if a second detector in the same logical zone triggers an alarm The transmission devices and notification appliances are activated Dual zone dependency If a detector triggers an initial alarm wit...

Страница 42: ...ight on the LED display lights up An internal buzzer sounds see also Switching off internal buzzer page 46 Depending on the configuration sounders and or visual notification appliances e g sirens strobes are activated If the transmission device to the fire department is activated the Transmission Device activated signal light lights up red 9 4 2 Displaying the detector zones in alarm state The num...

Страница 43: ...splay see also Resetting alarm message page 49 9 4 3 Sequence of the alarm messages The messages are displayed in chronological order The newest alarm message of a logical zone is always displayed at the end of the list The first and oldest alarm message of a logical zone is displayed at the beginning of the list The next three messages are displayed as you scroll through the list Notice 30 second...

Страница 44: ... total number of logical zones in which one or more detectors have triggered an alarm 9 4 6 Displaying the individual detectors in a logical zone To display the individual detectors in a logical zone select the logical zone you require The alarm messages for the individual detectors are listed 9 4 7 Information about individual detectors Each alarm message contains information about The element ca...

Страница 45: ...e information about an alarm message see Displaying additional information page 45 9 4 8 Displaying additional information Notice By way of example an action text can be entered for every detector type in the FSP 5000 RPS programming software To display further information about the individual detectors select the alarm message you require The following information is displayed Element category Me...

Страница 46: ...s have the highest priority compared with all other message types If a fire alarm is reported the system switches automatically to alarm indication 10 1 Optical and acoustic signals The red alarm signal light on the LED display lights up An internal buzzer sounds see also Switching off internal buzzer page 46 Depending on the configuration sounders and or visual notification appliances e g sirens ...

Страница 47: ...evice Only the activated signaling devices are displayed 1 Select one or more list fields The list field is marked 2 Select Reset The control units are reset to the initial state In the Control field on the status bar the number of control elements is reduced by the number of reset elements To reset transmission devices carry out the same steps but select Transmission device in step 1 10 6 Trigger...

Страница 48: ...e specified differently for each logical zone or detector Reset possible in Time span after which the detector can be reset For information on resetting see Resetting alarm message page 49 Caution If the time to acknowledge or the time to investigate is exceeded the alarm is immediately forwarded to external stations To initiate alarm verification select Acknowledge within the time shown to confir...

Страница 49: ...s that are not in the normal state All elements in this event to reset all elements that have triggered a fire alarm for example Logical zone a list of the logical zones is displayed Detector a list of the detectors is displayed To reset an alarm message select either Reset on the message display or The alarm message and Reset in the detailed view Depending on the variant that is offered see above...

Страница 50: ...9 User Guide Bosch Sicherheitssysteme GmbH 1 Select the alarm message you require 2 Select Bypass Notice The system does not transmit any information as to whether it was possible to bypass the selected element To monitor the operation please check the element ...

Страница 51: ...s grouped by message type is displayed The number of elements is also given in each case To display the fault messages select the message category you require in this case Fault 0 Fire 0 Control 8 Fault 0 Bypass Status Caution If a message does not have to be reset it is removed from the display as soon as the fault has been rectified Notice If individual elements that are combined with other elem...

Страница 52: ...nformation about Element category Message type Address of the element group Number of individual elements that have caused a fault in the respective element group Message number Additional information e g the installation location Example Fault Zone 00005 001 Office 1 6 Element category Different detectors in one logical zone Message type Fault Address of element groups 00005 The fifth logical zon...

Страница 53: ...tional information e g the installation location Example Fault Transmission device 00026 004 002 Cafeteria Element category Transmission device Message type Fault Element address The following transmission device has caused a fault 00026 004 The fourth transmission device 004 in the 26th group 00026 Message number The fault messages are numbered chronologically The message number in the second lin...

Страница 54: ...low signal light lights up see also Display elements page 20 Fault System Fault Transmission Device Fault Signals Acoustic signal An internal signal tone sounds on the system To temporarily switch off the internal buzzer Press the Signal tone off key The internal signal tone is switched off 11 3 Resetting malfunction message Caution If a message does not have to be reset it is removed from the dis...

Страница 55: ... all elements the standby display is displayed 11 4 Isolating an element In order to isolate an element that has caused a fault 1 Select the fault message you require 2 Select Block Caution The system does not transmit any information as to whether it was possible to isolate the selected element To monitor the operation check the element ...

Страница 56: ...ical zone Extinguishing system Annunciator Bypass group More Control element Interface module 12 2 Bypassing and un bypassing elements Select the element you require in the submenu Notice Partly bypassed elements such as loops or bypass groups can be displayed and completely bypassed see Displaying and un bypassing bypassed element groups page 57 Notice The menu structure may be different dependin...

Страница 57: ...element groups in the relevant element category 3 Select the list field you require e g logical zone 4 Select Partly bypassed to display all partly bypassed logical zones Completely bypassed to display all completely bypassed logical zones Depending on which option you select all partly bypassed or fully bypassed logical zones will be displayed The number in parentheses e g 5 specifies the number ...

Страница 58: ...s is displayed To un bypass bypassed elements 1 Select the elements you require 2 Select Un bypass 12 5 Bypassing Un bypassing buzzer In order to prevent an acoustic warning tone being sent to the panel during maintenance work for example the panel s internal buzzer can be permanently bypassed To bypass the internal buzzer select the following in the start menu 1 Bypass Block 2 Bypass 3 More 4 Byp...

Страница 59: ...he submenu Example To isolate a detector select the following in the start menu 1 Bypass Block 2 Block 3 Detector Various selection criteria are displayed See also Working with lists page 26 4 Select a selection criterion e g By description A list of the detectors is displayed Refer to Scrolling through lists page 27 for information on how to scroll forward and backward through the list 5 Select t...

Страница 60: ...of all isolated detectors is displayed To de isolate isolated elements 1 Select the element you require 2 Select Un block The element is de isolated 13 3 2 Via the status bar To display a list of all isolated elements 1 Select Bypass from the status bar A list of various states is displayed 2 Select Blocked A list of various element categories is displayed The listed figure indicates the number of...

Страница 61: ...ics Element details Modules Hardware Panel passport LED test on modules History log Network services VAS 14 2 Element details To display diagnostic information about the elements in a particular module 1 In the start menu select Diagnostics 2 Element details A list of the LSN modules is displayed Notice The numbers before the module names indicate the slot of the module on the panel 1 Select the l...

Страница 62: ...t A list of all used modules is displayed 4 Select the list field you require A list of various information options is displayed Module passport Module Compatibility Module status For an LSN module the following selection fields are also offered Module status and counters Reset counters 5 Select the information option you require e g Module status Diagnostic information about the module status is ...

Страница 63: ...ed on the touch screen If a key is pressed twice this key is shown with a black background Press the key again to display it without distinction 6 Select Stop key test to end the foil test Display test To test the operativeness of the display 1 In the start menu select Diagnostics 2 Hardware 3 Display 4 Select Display test First the display is filled with the colors black white red green and blue ...

Страница 64: ...s To test the LED display of selected modules 1 In the start menu select Diagnostics 2 LED test on modules A list of various selection criteria is offered Select LED test all modules to test the LED display of all modules Select By number or By type to test the LED display of individual selected modules Example To test the LED displays of an LSN 300 module 1 Select By type A list of all module typ...

Страница 65: ...om 1 to 64 can be assigned to panels All numbers above 240 241 255 are assigned dynamically and used for instance for an OPC server or a PC with FSP 5000 RPS software 14 7 2 Consistency check Inconsistencies between the network settings configured in FSP 5000 RPS and those set in the panel controller are displayed under Diagnostics Network services Consistency check 1 In the start menu select Diag...

Страница 66: ...ress of the network node you wish to assess as regards availability and select Send ping command To enter an IP address Touch the field containing the IP address Use the arrow keys on the operating panel to select the individual numbers and modify using the number keys on the alphanumeric keypad Or Touch the Change field Touch the field containing the number block to be changed Use the arrow keys ...

Страница 67: ...tenance and service functions possible with the Remote Programming Software FSP 5000 RPS can be done from remote e g Remote Terminal configuration of the panel trouble shooting Remote Alert If you enable the Remote Alert service an FPA 5000 FPA 1200 system pushes relevant status information and events e g alarms or fault messages to the Bosch Remote Portal In case of an unexpected event an alert c...

Страница 68: ...cure network Server IP address IP address of the server collecting and receiving data Server port Port number of the server collecting and receiving data If a Remote ID is set in the panel it automatically tries to connect to the Remote Portal For a manual connection attempt select Connect to server 14 8 Voice alarm systems Two different kinds of voice alarm systems can be connected to the FPA 500...

Страница 69: ... of the virtual VAS triggers virtual control inputs configured in the FSP 5000 RPS programming software and the VAS over IP configuration Compatibility Shows whether the version of the connected VAS over IP is released for the connection to an FPA 5000 FPA 1200 If a warning is displayed please check the version of the VAS over IP Connection fault counter Shows the number of connection errors to th...

Страница 70: ...ge display is via a shortcut see also Changing language display page 31 There are two ways of selecting a different language display Using the menu Entering a shortcut see Changing language display page 31 Notice After the system starts up following a power cut or battery failure the default language defined in the FSP 5000 RPS programming software is set again Making a selection via the menu 1 In...

Страница 71: ...lements 1 In the start menu select Maintenance 2 Activate transmission device 3 Select the list fields of the activated transmission devices 4 Select Off The transmission devices are no longer activated 15 5 Detector removal Notice To remove a detector all acoustic signals and transmission devices are bypassed for 15 minutes They are automatically un bypassed when the 15 minutes are up The acousti...

Страница 72: ...nge the device on the V 24 interface The device is ready for operation 15 7 Bypassing Un bypassing buzzer In order to prevent an acoustic warning tone being sent to the panel during maintenance work for example the panel s internal buzzer can be permanently bypassed To bypass the internal buzzer select the following from the start menu 1 Maintenance 2 Bypass buzzer The buzzer is bypassed and the t...

Страница 73: ...fined walktest groups consisting of at least one element There are 12 pre defined walktest groups The number of possible walktest groups is predefined January to December Example Detectors which are to be tested in May can be grouped together in a group called May New elements can be added to a group and elements that have already been added can be removed Notice Even if the elements in a group e ...

Страница 74: ...lement The element is marked 3 Select Add The selected element is added to the group Delete Old Select this function field to delete one or more elements Only elements from the selected walktest group are displayed 1 Select an element The element is marked 2 Select Delete The selected element is deleted from the group Example 1 Select Show Change To delete one or more element s from the selected g...

Страница 75: ...d enter the number of the element into the search screen see also Search Function Element page 29 Notice If you select the element category Loop Logical zone Detector or Walktest group you will be asked to select the type of walk test Select Sequential walktest to check each individual sensor optical chemical or thermal of the detectors you are testing or select Simultaneous walktest to test combi...

Страница 76: ... reaction 16 5 Assigning tested elements to a walktest group Notice Only those elements in the current walktest that have been tested can be assigned to a different walktest group On completion of the walktest you can assign the tested elements to a different walktest group for the next walktest for example 1 Select Exit from the status bar Various possibilities are offered on the display Select A...

Страница 77: ...ime Event types Message types such as Fault Device types Device types such as Detectors Address range Address range within a system User commands Selected function fields such as Acknowledge or Reset Walktest Elements switched to walktest mode If one or more filters have been set the Change filter field in the status bar is highlighted in a dark color 17 2 Setting filters To display only particula...

Страница 78: ...the selection list 5 Select the desired device types from the displayed list 6 Repeat steps 4 to 5 until all desired filters have been selected To display all filtered data of the combined filters 7 Select Show filter result 17 5 Status bar functions The following functions are offered To switch to the status bar on the start page press the double arrow key in the status bar or on the membrane key...

Страница 79: ...ng a particular area via the entry of the event numbers 2 Select Define range Two possibilities are offered on the display 3 Activate the checkbox in front of one of the two options Number of events to be printed starting from latest event For the printout enter a particular number of events counted from the most recent event Event numbers to be printed To print out a particular range specify by e...

Страница 80: ...least one panel in the network is in day mode Standalone Network Night mode Panel is in night mode All networked panels in the network scope are in night mode Day mode Panel is in in day mode Night day combination Panel is in night mode but at least one other panel in the network scope is in daymode Notice Please note that following a transmission fault it may be necessary to synchronize the day n...

Страница 81: ...tched to day mode To display a list of all detector groups in day mode 1 In the start menu select Switch to day mode or Switch to night mode depending on which mode the panel is currently in or select the day mode or night mode icon on the status bar 2 Select Show details A list of all logical zones that are switched to day mode is displayed 18 3 Changing the time for resetting to night mode Cauti...

Страница 82: ... Select OK to confirm the entry or Cancel to cancel the operation The entries are confirmed To change the set back time in day mode to night mode 1 On the status bar select 2 or In the start menu select Switch to night mode 3 Select Change time 4 Enter the numbers you require Refer to Entering numbers and text page 29 for information on how to enter numbers 5 Select OK to confirm the entry or Canc...

Страница 83: ...The following can be carried out on the panel controller Elements can be added to or removed from input or output groups Input or output groups can be renamed 19 2 1 Adding or deleting elements Input group In order to add elements to an input group or remove elements from it 1 In the start menu select Configuration 2 Set input output groups 3 Input group Two different lists are displayed See Worki...

Страница 84: ... element The element is marked 3 Select Add The selected element is added to the group Delete Old Select this function field to delete one or more elements Only elements from the selected input group are displayed 1 Select an element The element is marked 2 Select Delete The selected element is deleted from the group Example 1 Select Show Change To delete one or more element s from the selected gr...

Страница 85: ...group in question Refer to Scrolling through lists page 27 for information on how to scroll forward and backward through the list 5 Select the list field you require You can choose between various options To add elements to a group or remove elements from it see Adding or removing page 85 Isolate Group To display the elements in a block group and to delete or add elements repeat the steps but sele...

Страница 86: ...ed for each access level in the FSP 5000 RPS programming software This means that all operators with access authorization for the second level receive the same password for example The password for access levels two to four can be changed If each user uses a different password Change operator data Change the password for an operator Set default password Reset a user password to the following numbe...

Страница 87: ...screen is displayed 4 Enter a new name Refer to Entering numbers and text page 29 for information on how to enter text 5 Select OK to confirm the entry or Cancel to cancel the operation The event with the new name is displayed on the list 19 7 Network services 19 7 1 Ethernet You can modify and activate the network settings IP settings Ethernet redundancy of panels and remote operating panels that...

Страница 88: ...ntry choose Clear Confirm with OK and return to the Network services screen To leave the screen without saving changes choose Cancel 6 The System ID is assigned to the panel by the Remote Portal Normally it is not necessary to change it In case you need to change it choose Change System ID Enter the System ID 9 digit via the alphanumeric keys on the keypad 7 Confirm with OK and return to the Remot...

Страница 89: ...e are accepted into the system 20 3 Master password Notice With the master password all functions can be operated and passwords and names can be changed One of the following two options is offered Entering a master password that is valid indefinitely This password cannot be changed and is available from the relevant Bosch branch on request Entering a master password that is valid for a specified p...

Страница 90: ...he Support department 6 Once you have received the 24 hour password from the Support department select Enter password 7 Enter the password The 24 hour master password is accepted and the user is logged on Change password To change passwords select Change password Additional options may be offered See also Operator page 86 20 4 Remote Services Remote connection Notice If another menu is called up w...

Страница 91: ...ce If all operators with the same access authorization have the same password this function cannot be used 1 In the start menu select Further functions 2 Change password A list of all operators is displayed Refer to Scrolling through lists page 27 for information on how to navigate through a list 3 Select the list field you require 4 Enter the password On the display each digit of the password is ...

Страница 92: ... alarm and or the fire drill have been completed 20 7 Alarm Counters Show Lifetime Event Counters During the lifetime of the panel the following alarm messages are counted External alarm all fire messages Internal alarm all alarm messages that the panel receives in day mode Walktest alarm all messages from detectors switched to walktest To display the number of alarm messages which have been count...

Страница 93: ... the same function 21 1 Menu overview Reset Event type Scope Logical zone Detector This panel 21 2 Resetting elements To reset a detector or logical zone for example 1 In the start menu select Reset 2 Select the element you require 3 Select the detector or zone Refer to Scrolling through lists page 27 for information on how to navigate through a list 4 Select the required list fields The list fiel...

Страница 94: ...information on how to navigate through a list 3 Select the list field you require The submenu of the selected function or device description is displayed 22 3 Search element To search for an element which is connected to the system 1 In the start menu select Search function element 2 Go to element Three different lists are offered See also Working with lists page 26 3 Select a list e g By descript...

Страница 95: ...0 Changing time for resetting to night mode 81 Checking access authorization 25 Configuration version 88 Consistency check 65 Country 88 D Day mode 42 80 Day night mode showing details 81 Day night mode switching 80 Default language 70 De isolating elements 59 Deleting numbers 31 Description search by 29 Detector removal 71 Detector sensitivity 85 Diagnostics 61 Diagnostics address cards 62 Diagno...

Страница 96: ...t assigning mode 28 List select 28 Lists 26 Lists scrolling 27 Logging in 24 Logging out 25 Logical addressing 31 M MAC Address 64 Master password 89 N Network 65 Network addressing 33 Networking establish remote connection 34 Networking terminating remote connection 34 Night mode 41 80 Node number 65 Number search by 29 O Operating elements 19 Operator 86 Optical acoustic signals 42 Output group ...

Страница 97: ...upport service address 23 SW Version 64 Switching external signaling devices off 47 Switching external signaling devices on 47 Switching off internal buzzer 46 Switching status bars 31 T Time to acknowledge 48 Time to investigate 48 Time zone 88 Touch screen 10 22 Triggering alarm manually 49 Triggering fire verification 47 Types of alarm 40 U Un bypassing bypassed element groups 57 Un bypassing e...

Страница 98: ...98 en Index Panel Controller 2017 09 7 0 F 01U 258 929 User Guide Bosch Sicherheitssysteme GmbH ...

Страница 99: ......

Страница 100: ...Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany www boschsecurity com Bosch Sicherheitssysteme GmbH 2017 ...

Отзывы: