1 MPC-8000-C and FMR-5000-C-08
1.1 Intended Use
The Panel Controller MPC-8000-C and the Remote Keypad FMR-5000-C are the central element of the fire panel.
They control the fire panel and every component connected to the panel. All kind of messages are indicated on the
high-resolution touch-screen and can intuitively be operated and processed.
1.2 Technical Data
Operating voltage MPC
20 V DC to 30 V DC
Operating voltage FMR
12 V DC to 30 V DC
Max. current consumption
–
Standby operation
135/140 mA @ 24 V DC
–
In the event of an alarm
225/230 mA @ 24 V DC
Max. cable length
–
CAN networking
1000 m
depending on configuration, topology and cable type
–
Ethernet/IP networking with fibre
24 to 40 km
Display element
14.5 cm (5.7") multi-color TFT display with 320 x 240
pixels
Operating element
Touch screen with 127.5 mm x 170 mm active surface
Interfaces
CAN1, CAN2, ETH1, ETH2, USB, RS232
Signal inputs
IN1/IN2
Dimensions MPC (H x W x D)
190 mm x 404 mm x 60 mm
Dimensions FMR (H x W x D)
280 mm x 340 mm x 87 mm
Weight MPC
ca. 2 kg
Weight FMR
ca. 3 kg
1.3 Rules and Conditions
Installation and Operation
Installation must only be carried out by trained and skilled personnel. Please follow your local
regulations concerning installation.
Operation of the devices is not intended for personal, family or household use and applications.
Live components and stripped cable! Risk of injury from electric shock. The system must be current-
free during connection work.
F.01U.317.525
Bosch Sicherheitssysteme GmbH
2015.10 | version 1.0 | 1