3 6 |
FHP560 Controller
Applications Manual
Bosch Thermotechnology Corp.
Data subject to change
Page____ of ____
14 ZS Combination Sensors
14.1 ZS Sensor Overview
The Bosch line of intelligent zone sensors provides the function and
fl
exibility you need to manage the conditions important to the comfort and
productivity of the zone occupants. The ZS sensors are available in a variety of zone sensing combinations to address most application needs.
These combinations include temperature, relative humidity, and indoor air quality (carbon dioxide). They are built to be
fl
exible, allowing for easy
customization of what the user/technician sees. Designed to work with the FHP560 controller, the ZS sensor line includes the ZS Standard, ZS
Plus, and ZS Pro.
ZS Pro
ZS Plus
ZS Standard
Fig. 6 ZS Sensors
Available Features
Features
ZS Standard
ZS Plus
ZS Pro
Temperature Only
Temperature and Humidity
Temperature, CO
₂
, and Humidity
Neutral color
Addressable / supports daisy-chaining
DIP Switch Addressable
Hidden communication port
Mounts on a standard 2” by 4” electrical box
Occupancy status indicator
Push-button occupancy override
Temperature set-point adjustment
Humidity set-point adjustment
Large, easy- to-read LCD
Alarm indicator
Info and Mode Button Support
Indication of Energy Savings
Deg F/C Changeover at the Sensor
On/Off Button; not just TLO
Custom Unit Information on Display (Text and/or Icons)
Table 38
Models and Part Numbers
Sensor Model
Description
Bosch Part Number
ZS-FHP
Standard Zone Sensor, no options, FHP Logo
8 733 933 902
ZS-H-FHP
Standard Zone Sensor, w/ Humidity FHP Logo
8 733 933 903
ZSPL-FHP
Plus Zone Sensor with override, slide pot and occupied LED no options FHP Logo
8 733 933 901
ZSP-FHP
Pro Zone Sensor with LCD Display no options FHP Logo
8 733 933 898
ZSP-H-FHP
Pro Zone Sensor with LCD Display w/ Humidity FHP Logo
8 733 933 899
ZSP-HC-FHP
Pro Zone Sensor with LCD Display w/ Humidity and CO
₂
FHP Logo
8 733 933 900
Table 39
14.2 ZS Sensor Speci
fi
cations
Speci
fi
cations
Description
Sensor Type / Options
Value
Sensing element range and accuracy
Temperature only
Range: 32 to 122°F (0 to 50°C)
Accuracy: ±0.35°F (0.2°C)
Temperature if humidity is included
Range: 50 to 104°F (10 to 40°C)
Accuracy: 0.5°F (0.3°C)
Options:
Humidity:
Range: 10 to 90%
Accuracy: 2% typical
CO
₂
:
Range: 0 to 2000 PPM
Accuracy: ±75 PPM typical
Power requirements
Temperature only - ZS Standard or ZS Plus:
12 Vdc @ 6 mA
Temperature with humidity - ZS Standard or ZS Plus:
12 Vdc @ 7 mA
Temperature with humidity and CO
₂
- All models
12 Vdc @ 15 mA (idle) to
190 mA (CO
₂
measurement cycle)
Temperature and CO
₂
- All models
12 Vdc @ 14 mA (idle) to
189 mA (CO
₂
measurement cycle)
Power supply
―
The 4-conductor Rnet cable from a controller su12 Vdc @
210 mA. For additional power, use an external power supply. Use
the above power requirements to calculate the size of the external
power supply.
Communication
―
115 kbps
Local access port
―
For local access to start up and troubleshoot the system
Environmental operating range
―
-4 to 122°F (-20 to 50°C), 10 to 90% relative humidity, non-
condensing
Mounting
―
Standard 4x2-in. electrical box using the 6-32 x 1/2” mounting
screws provided
Overall dimensions
Temperature sensor or temperature with humidity
sensor
Width: 3 in. (7.62 cm)
Height: 4-13/16 in. (12.22 cm)
Depth: 13/16 in. (2.01 cm)
Sensor with CO
₂
Width: 2-7/8 in. (7.3 cm)
Height: 4-13/16 in. (12.22 cm)
Depth: 1-1/4 in. (3.18 cm)
Table 40