15.3 Connecting the BACview to FHP560
Connect the BACview module (or laptop if using Virtual BACview) to the serial port on the DDC controller, or to a ZS wall-mounted sensor
connected to the controller (See Fig 26).
Fig.
26 Connecting BACview
15.4 To Communicate Using a Laptop & Virtual BACview
In lieu of using the hand-held module to interface with the FHP560, a connection may be established at the local access port of the controller, or at
the access port of a ZS Combo Sensor connected to the controller, to perform test and balance or to make changes to any device on the network.
Prerequisites:
Laptop with USB port
USB Link (part# 8733927403)
Using a USB Link:
1. If your computer does not already have the USB Link driver installed, install it before you connect the USB Link to your computer. The latest driver
may be obtained at the Bosch website.
a) Put the USB Link Driver CD into your laptop.
b) Run the .exe to install the driver. Accept all of the wizard’s default settings.
2. Connect the USB-L to the computer and to the controller’s Local Accesss port.
Fig.
27 Connecting to Laptop
3. Start the Virtual BACview® application (software available for download from
the Bosch website.
).
4. In the Row Count
fi
eld, enter the number of screen rows you want displayed (100 maximum).
5. In the Comm Port
fi
eld, select the laptop’s comm port that the USB Link is connected to. To
fi
nd the port number, select Start > Control Panel
> System > Hardware > Device Manager > Ports (Com & LPT). The COM port number is beside CP210x USB to UART Bridge.
Fig.
28
6. Click
OK.