DIVAR IP 7000 (3U)
Maintenance | en
49
Bosch Sicherheitssysteme GmbH
Installation Manual
2016.08 | V2.1 | DOC
LED status:
–
Amber lighted LED: The power supply is off.
–
Green lighted LED: The power supply is operating.
1
1
Release tab
To replace the power supply:
1.
You can leave the unit running and remove only one power supply if your chassis includes
a redundant power supply.
2.
Unplug the AC power cord of the failed power supply.
3.
Push the release tab (on the back of the power supply) as illustrated.
4.
Pull the power supply out using the handle provided.
5.
Replace the failed power module with the same model.
6.
Push the new power supply module into the power bay until you hear a click.
7.
Plug the AC power cord back into the module and turn on the unit.
10.14
Monitoring the system
The system provides tools for health monitoring.
To activate the monitoring functionality:
1.
Turn on the unit and log on as user BVRAdmin. The default screen is displayed.
2.
Double-click the
SuperDoctor 5
service icon on the screen.
3.
Log on to the web interface using the following default credentials:
User Name: ADMIN
Password: ADMIN
4.
Click the
Configuration
tab, then click
Password Settings
and change the default
password.