D9412GV2/D7412GV2
|
Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04
69
Appendix A: System Wiring Diagrams, Issue A
A.1
D9412GV2 Control Panel
Figure 38: D9412GV2, Power Supply Side
TELC O
RI NG
TI P
PH ONE LIN E
SEIZ ED
+
AUX PWR
ALARM TRIG
COM
SUPV IN
ALARM CKT
-
-
+
D113
BAT 2+
BAT 1+
BAT 2 -
BAT 1-
SUPV
CHGR+
CHGR-
VAUX+
-
+
-
+
-
+
EARTH GROUND
CO MMON
BATTERY NEGATIVE ONLY
M ax im um Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
1
2
3
4
5
6
7
8
9
1 0
C LA SS 2 T RA N SF OR M E R
16. 5 VA C 4 0 VA 60 H z
M od el D 164 0
I nt er na ll y Fu sed - Do N ot sho r t
R equ ir es U ns w it ch ed O ut l et
D o No t S har e Wi t h O th er Equ i pm en t
GROUND FAULT DETECT
Ena bled
Dis abled
1 2
11
1 3
Po in t 1
P oi nt 2
1 5
1 4
16
Po in t 3
P oi nt 4
PH ON E
LE D
R E D
ON w hen
comm uni cat i ng
OF F w he n i dl e
PH ON E LI NE S EI ZED
TI P
R IN G
TELC O CO RD
M ODE L D 161
GRN
P oi nt 8
S 3 O pt i on
C lo sed = 1K
Ω
E OL
N or m al O per at i on
O pen = AB -1 2 U L
B el l Bo x
2 20 K
Ω
D5 200/ D5 360
PR O G CO N N
PROGRAMM ABLE
ALARM OUTPU TS
Te rm ina ls
SWITCHED AUX
a nd
6
7
Te rminal
8
11
13
14
16
12
10
2
6
7
9
6
6
2
2
2
3
2
5
4
6
6
6
8
15
D9412GV2
1 - If required by local AHJ, connect D113 Battery
Lead Supervision Module.
2 Batteries
3 - D122 Dual Battery Harness, as required
4-
D1640 Transformer and D8004 Transformer
Enclosure required for NFPA Applications
5 - D8132 Dual Battery Charger with two batteries
(Batteries are not supervised.)
6 - Power limited, supervised
7 - Power limited
8 - D192G Bell Supervision Module
9 - To Relay A or Relay B
10 - Listed Audible Signaling Devices rated at
12.0 VDC nominal (Do not use vibrating type
horns.)
11 - C900V2 or C900TTL-E (optional)
12 - RJ31X, secondary phone line
13 - 560
Ω
, 2 W EOL Resistor
14 - RJ31X, primary phone line
15 - D928
16 - To earth ground
All external connections except Terminal 5 (battery positive) are power limited.