D7050DH
|
Installation Instructions | 9.0 Specifications
6
Bosch Security Systems, Inc. | 9/06 | 49325E
5.
With the chamber cover removed, clean te inside
of the cover with a vacuum or clean dry
compressed air.
Do not clean the D7050DH components
with water or any liquid cleaner.
6.
Replace the chamber cover and ensure the hole for
the LED is properly aligned over the LED. Place
the cover parallel to the chamber and gently snap
the locking tabs into place.
7.
Replace the D7050DH’s cover, lining up the holes
for the LED.
8.
Return the D7050DH to its base and replace the
D343’s cover.
After cleaning, test the D7050DH for
proper calibration. Refer to
Section 7.0
Testing
beginning on page 4.
Do not paint the D7050DH. Paint or other
foreign matter covering the screens can
stop or delay smoke from entering the
detector.
9.0
Specifications
Table 3: column width table
Standby
Current
Refer to the
D343 Installation
Instructions
(P/N: 48199), the
DS9400M
Reference Guide
(P/N: 44578), and the
DS6431 Installation Instructions
(P/N: 41381)
Alarm
Current
Refer to the
D343 Installation
Instructions
(P/N: 48199), the
DS9400M
Reference Guide
(P/N: 44578), and the
DS6431 Installation Instructions
(P/N: 41381)
Minimum
Operating
Voltage
8 VDC peak
Power-Up
Time
22 sec (maximum)
Installation
Temperature
+32°F to +100°F (0°C to +38°C)
Relative
Humidity
0% to 93% (non-condensing)
Required
Accessories
D343 Duct Housing and Sample Tube
Options
D344-RT Remote Test
D344-RL Remote LED
SMK-TM Test Magnet