D7050DH 

|

 

Installation Instructions | 1.0  Description 

 

Bosch Security Systems, Inc. | 9/06 | 49325E 

 

Notices 

These instructions cover the installation of the 
D7050DH Multiplex Photoelectric Duct Smoke 
Detector on a D7024 or a DS9400M 24 VDC Fire 
Alarm Control Panel (FACP) with a D7039 or DS9431 
Multiplex Expansion Module installed. The D7024 and 
DS9400M requires ROM version 2.0 or greater. 

Install, test, and maintain the D7050DH according to 
these instructions, NFPA 72, local codes, and authority 
having jurisdiction (AHJ). 

 

Follow the procedures in these instructions 
to avoid personal injury and damage to the 
equipment. Failure to follow these 
instructions can result in the D7050DH not 
operating properly. Bosch  is not 
responsible for improperly installed, tested, 
or maintained devices. 

The D7050DH complies with Part 15 of the Federal 
Communications Commission (FCC) Rules and with 
the RSS-210 of Industry and Science Canada. 
D7050DH operation is subject to the following two 
conditions: 

1.

 

It does not cause harmful interference. 

2.

 

It must accept any interference it receives, 
including interference that might cause undesirable 
operation. 

1.0  

Description 

The D7050DH (

Figure 1)

 is Underwriters Laboratories, 

Inc. (UL) Listed and requires a D343 Duct Detector 
Housing. Use this detector with the D7024 or a 
DS9400M that includes a D7039 or DS9431 Multiplex 
Expansion Module. 
An LED indicator on the head flashes every 3 to 8 sec 
to ensure the D7050DH has power and the smoke 
sampling circuitry functions. This LED flashes at least 
once each second during an alarm confirming 
individual detector alarms. The D7050DH 
automatically resets after the alarm condition clears.  

2.0 Installation 

For installation details, refer to the 

D7024 FACP 

Operation and Installation Guide

 (P/N: 31499), the 

D9400M Reference Guide

 (P/N: 44578), the 

D7039 

Installation Guide

 (P/N: 38685), or the D

S9431 

Installation Instructions

 (P/N: 41381). 

 

 

Do not exceed the maximum line resistance 
of 50

 

Figure 1: 

D7050DH 

4 in.

(10.2 cm)

1.5 in.

(3.8 cm)

1

2

3

4

5

6

 

1 -  Side view 

2 -  Top view 

3 -  Alarm/Test LED 

4 -  Magnetic test locator 

5 -  Calibration voltage pins 

6 -  Tamper screw hole 

 

Table 1:      Maximum Wire Length Allowed for 

each Multiplex Bus 

 

 

 

 

Wire Gauge

 

Maximum 50 

 for each  

Bus Loop 

18 AWG (1.02 mm) 

3800 ft (1170 m) 

16 AWG (1.29 mm) 

5950 ft (1810 m) 

14 AWG (1.63 mm) 

5950 ft (1810 m) 

12 AWG (2.05 mm) 

5950 ft (1810 m) 

 

Table 2:      Maximum Number of Detectors 

Allowed for each Multiplex Bus 

 

 

 

 

With Remote Test 

40 

With Remote LED 

50 

Without Annunciator 

70 

 

 

Do not use shielded cable. 

 

Содержание D7050DH

Страница 1: ...EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D7050DH ...

Страница 2: ...n The D7050DH Figure 1 is Underwriters Laboratories Inc UL Listed and requires a D343 Duct Detector Housing Use this detector with the D7024 or a DS9400M that includes a D7039 or DS9431 Multiplex Expansion Module An LED indicator on the head flashes every 3 to 8 sec to ensure the D7050DH has power and the smoke sampling circuitry functions This LED flashes at least once each second during an alarm...

Страница 3: ...ation and Installation Guide P N 31499 or the DS9400M Reference Guide P N 44578 for additional address limitations Figure 3 Setting the D7050DH Address 0 5 1 2 3 4 6 7 8 9 0 5 1 2 3 4 6 7 8 9 0 2 1 2 0 1 A B 1 2 3 1 Hundreds 2 Tens 3 Ones A D7024 FACP B DS9400 FACP For example 0 hundreds 9 tens 5 ones Address 95 on the D7024 FACP The A address range works on the D7039 Multiplex Expansion Module wi...

Страница 4: ...g to the next detector 7 2 Sensitivity Testing Calibration is important in determining a detector s continued operation Depending on local regulations calibration testing might be required more than once a year According to NFPA72 perform a Calibration Test at installation and every other year thereafter Perform a Functional Test monthly Test the D7050DH s sensitivity to meet NFPA 72 requirements ...

Страница 5: ...red by the voltmeter is half the sensitivity in ft obscuration of the D7050DH b Multiply the voltage by 2 The result must be within the factory marked calibration range printed on the label located on the bottom of the D7050DH c If the D7050DH is outside the factory marked calibration range remove it and clean it Or replace it as described in Section 7 1 Operational Testing d After cleaning rechec...

Страница 6: ...ion Refer to Section 7 0 Testing beginning on page 4 Do not paint the D7050DH Paint or other foreign matter covering the screens can stop or delay smoke from entering the detector 9 0 Specifications Table 3 column width table Standby Current Refer to the D343 Installation Instructions P N 48199 the DS9400M Reference Guide P N 44578 and the DS6431 Installation Instructions P N 41381 Alarm Current R...

Страница 7: ...D7050DH Installation Instructions Bosch Security Systems Inc 9 06 49325E 7 Notes ...

Страница 8: ... 2006 Bosch Security Systems Inc 49325E Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 ...

Отзывы: