D7050DH
|
Installation Instructions | 1.0 Description
2
Bosch Security Systems, Inc. | 9/06 | 49325E
Notices
These instructions cover the installation of the
D7050DH Multiplex Photoelectric Duct Smoke
Detector on a D7024 or a DS9400M 24 VDC Fire
Alarm Control Panel (FACP) with a D7039 or DS9431
Multiplex Expansion Module installed. The D7024 and
DS9400M requires ROM version 2.0 or greater.
Install, test, and maintain the D7050DH according to
these instructions, NFPA 72, local codes, and authority
having jurisdiction (AHJ).
Follow the procedures in these instructions
to avoid personal injury and damage to the
equipment. Failure to follow these
instructions can result in the D7050DH not
operating properly. Bosch is not
responsible for improperly installed, tested,
or maintained devices.
The D7050DH complies with Part 15 of the Federal
Communications Commission (FCC) Rules and with
the RSS-210 of Industry and Science Canada.
D7050DH operation is subject to the following two
conditions:
1.
It does not cause harmful interference.
2.
It must accept any interference it receives,
including interference that might cause undesirable
operation.
1.0
Description
The D7050DH (
Figure 1)
is Underwriters Laboratories,
Inc. (UL) Listed and requires a D343 Duct Detector
Housing. Use this detector with the D7024 or a
DS9400M that includes a D7039 or DS9431 Multiplex
Expansion Module.
An LED indicator on the head flashes every 3 to 8 sec
to ensure the D7050DH has power and the smoke
sampling circuitry functions. This LED flashes at least
once each second during an alarm confirming
individual detector alarms. The D7050DH
automatically resets after the alarm condition clears.
2.0 Installation
For installation details, refer to the
D7024 FACP
Operation and Installation Guide
(P/N: 31499), the
D9400M Reference Guide
(P/N: 44578), the
D7039
Installation Guide
(P/N: 38685), or the D
S9431
Installation Instructions
(P/N: 41381).
Do not exceed the maximum line resistance
of 50
Ω
.
Figure 1:
D7050DH
4 in.
(10.2 cm)
1.5 in.
(3.8 cm)
1
2
3
4
5
6
1 - Side view
2 - Top view
3 - Alarm/Test LED
4 - Magnetic test locator
5 - Calibration voltage pins
6 - Tamper screw hole
Table 1: Maximum Wire Length Allowed for
each Multiplex Bus
Wire Gauge
Maximum 50
Ω
for each
Bus Loop
18 AWG (1.02 mm)
3800 ft (1170 m)
16 AWG (1.29 mm)
5950 ft (1810 m)
14 AWG (1.63 mm)
5950 ft (1810 m)
12 AWG (2.05 mm)
5950 ft (1810 m)
Table 2: Maximum Number of Detectors
Allowed for each Multiplex Bus
With Remote Test
40
With Remote LED
50
Without Annunciator
70
Do not use shielded cable.