D621 Series
|
User's Guide | Turn The System On With Points Faulted (Force Arm)
Bosch Security Systems | 8/04 |
26
Turn The System On With Points
Faulted (Force Arm)
Force-arming is not permitted in UL applications.
1.
To force arm the system All On or Part On with the
normal Exit Delay time and tone, press [All On] or [Part
On]. The faulted point’s LED indicator remains on. The
Cmd indicator turns on. Press [All On] or [Part On] again.
If the Cmd indicator flashes fast, enter your passcode. The
All or Part indicator turns on, indicating the system is
turning All On or Part On. The Exit Delay Time
countdown begins with the exit tone. The faulted point’s
LED indicator flashes indicating that this point is force-
armed.
2.
To force arm the system All On or Part On with doubled
Exit Delay time and no exit tone, press and hold [All On]
or [Part On] until the Cmd LED lights (after
approximately one second). The faulted point’s LED
indicator remains on. Press [All On] or [Part On] again. If
the Cmd indicator flashes, enter your passcode. The All
or Part indicator turns on, indicating the system is turning
All On or Part On. The Exit Delay Time countdown is
doubled and begins without the exit tone. The faulted
point’s LED indicator flashes indicating that this point is
force-armed. Once the panel is armed, the Cmd indicator
turns off.
The system “forces” the faulted points on. As long as they
remain faulted they do not provide protection. If they
return to normal before the system is turned off they
provide protection and are capable of starting alarm
events. If a point becomes faulted after the exit delay
begins, the keypad displays the faulted point. If the point
remains faulted at the end of exit delay, it starts an alarm
event.