Conettix Universal Dual Path Communicator
Maintenance and troubleshooting | en
87
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
Flash pattern
Function
Flashing
Indicates a communication trouble. Verify IP address
and port numbers used by the central station. If it was
running correctly and now shows this indication, check
to make sure the account is enabled in the receiver or if
there is an IP path problem preventing the B465 from
reaching the receiver.
Flashing
Indicates multiple communication errors. Check the
B465 USB status menu for additional information to
help correct the problem.
On Steady
Indicates all non IP communication troubles. For
example low, or missing battery, phone lines are off the
hook for more than 2 minutes, or there is a
configuration issue.
Tab.
11.14:
SYSTEM TROUBLE LED descriptions
POWER LED
Flash pattern
Function
On Steady
Indicates a good Input Power level.
Flashing
Indicates Input Power is low (brownout) or failure.
Off
Is in an off state during the power up sequence.
Tab.
11.15:
POWER LED descriptions
BATTERY LED
Flash pattern
Function
Off
Indicates normal operations.
Flashing (one flash)
Indicates low battery voltage.