Conettix Universal Dual Path Communicator
System overview | en
11
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
–
Pulse 4/2 (1400 Hz ACK Tone)
–
SIA (SIA8, SIA20)
The B465 links the control panel’s PSTN dialer to the internet and then to one of the Bosch
Conettix receivers. The B465:
–
Connects with the control panel PSTN dialer (through the B465 panel line terminals) or
the control panel relay outputs connected to the B465 inputs.
–
Embeds alarm reports in Conettix IP reports and sends them to a Conettix D6600, D6100i
or D6100IPv6 Communications Receiver/Gateway through an IP network.
–
The Conettix receiver replies to the B465 with an acknowledgement report.
–
The B465 sends an acknowledgement back to the control panel through the PSTN
interface which completes the signal transmission
Refer to the following illustration for component locations on the B465.
2
3
7
13
15
1
4
5
8
9
6
10
11
T
MPR
BAT
ET
H
ER
N
E
T
EXT
E
R
N
A
L
A
N
N
U
N
C
X
MODULE 1
Y
MODULE
RELEASE
1 COM 2
3 COM 4
T R
PNL LINE 1
C NO
OUTPUT 2
+ BAT -
- +
NO C NC
OUTPUT 1
TRBL
TX
RX
AC
PANEL
LINE 2
USB
ETHERNET
100BASE-T
LINK
COMMUNICATION MODULE 1
3 COM 4
1 COM 2
R Y G
B
SDI2
Device Bus
24 VDC
or
16.5VAC
BATTERY
PANEL
LINE 1
BATTERY
AC
RX
TX
SYSTEM TROUBLE
INPUTS
2.2 k End of
Line Resistors
C NO
OUTPUT 3
12V
AUX COM
16
12
14
T R
PNL LINE 2
16.5VAC
Figure
3.2: Module overview
Call out - description
1
- Plug-in stabilizing holes (X,Y) - the plug-in cellular communicator modules compatible
with the B465 use the X hole.
2
- Plug-in module connector - for compatible plug-in cellular communicator modules.
3
- Plug-in module retention clip - pull the tab towards you to install or release plug-in
cellular communicator modules.
4
- On-board Ethernet connector - for wired IP communication with D6600 or D6100IPv6
central station receiver.
5
- USB connector - for temporary connection to a computer for B465 configuration, status,
and diagnotics.
6
- Status LEDs (SYSTEM TROUBLE, TX, RX, POWER, BATTERY) - these LEDs show system
troubles, Ethernet transmit (TX) and receive (RX) traffic, and the status of the primary power
source and the battery.
Содержание B465
Страница 1: ...Conettix Universal Dual Path Communicator B465 en Installation and Operation Manual ...
Страница 2: ......
Страница 114: ......