** AMAX 3000 / 3000 BE / 4000
*** AMAX 3000
O
1
2
3
4
5
6
D I P
N
On
Off
Figure 4.3: DX2010 DIP Switch Settings
Notice!
When the data bus address is changed, the module and the panel need to be re-powered to
enable the new address
Wiring
The following table and graphic show how to wire DX2010 to the option bus of the AMAX
panel.
Do not use twisted pair or shielded cables to connect DX2010 to the AMAX panel.
Power Supply
Wire diameter of 0.8mm
Wire diameter of 1.2mm
AMAX panel
30m
76m
AMAX panel (DX2010 out not
used)
305m
610m
External power supply
305m
610m
Table 4.6: Lengths of cable for DX2010
+
12V
AMAX 3000 BE / 4000
Y
R
Y
G
B
R
B
G
_
R
B
G
Y
1 COM
TMPR
R
B
G
Y
1 COM
TMPR
AMAX 2100 / 3000
DX2010
DX2010
Figure 4.4: Connecting DX2010 to the AMAX panel
Status Indicator
LED Condition
Denotation
On
Trouble Condition:
–
Grounding Conductor is not connected or there is a
communication failure between the module and the AMAX
panel
–
No zones distributed
–
Module address setting error
4.3.3
4.3.4
AMAX panel
Optional Modules and Peripheral Devices | en
17
Bosch Sicherheitssysteme GmbH
Installation Manual
2015.05 | 06 | F.01U.309.277