Notice!
The maximum number of keypads to be added to one option bus is 8.
Status Indicator
If all indicators of the keypad are flashing, the keypad loses connection to the AMAX panel.
DX2010
General
The AMAX panel supports DX2010 input expansion modules. Each expansion module supports
up to 8 zone inputs.
For information on the installation, refer to Module Installation, page 26.
Address Setting
Each DX2010 module connected to the AMAX panel needs its own data bus address.
Data Bus Address
Zones
102***
9 - 16
103**
17 - 24
104**
25 - 32
105*
33 - 40
106*
41 - 48
107*
49 - 56
108*
57 - 64
Table 4.4: DX2010 Address Settings
DIP Switch
S1
S2
S3
S4
S5
S6
Data Bus Address
32
16
8
4
2
1
102***
Off
Off
Off
Off
Off
On
103**
Off
Off
Off
Off
On
Off
104**
Off
Off
Off
Off
On
On
105*
Off
Off
Off
On
Off
Off
106*
Off
Off
Off
On
Off
On
107*
Off
Off
Off
On
On
Off
108*
Off
Off
Off
On
On
On
Table 4.5: DX2010 DIP Switch Settings
* AMAX 3000 BE / 4000
4.2.4
4.3
4.3.1
4.3.2
16
en | Optional Modules and Peripheral Devices
AMAX panel
2015.05 | 06 | F.01U.309.277
Installation Manual