56
Alarm Code:21
because of BUS.
BUS Under Voltage
Alarm Code:22
Indicates that the UPS get
BUS under voltage fault
The UPS transfers to Bypass
mode if supporting the load
BUS Unbalance
Alarm Code:23
Indicates that the positive
BUS voltage and negative
BUS voltage are too
lopsided to fault
The UPS transfers to Bypass
mode if supporting the load
BUS Short
Alarm Code:24
Indicates that the BUS
voltage decrease very
fast
Contact your service
representative
BUS Softstart Fail
Alarm Code:25
Indicates that the BUS
could not soft start
successfully
Contact your service
representative
Inv Over Voltage
Alarm Code:32
Indicates that the UPS get
invert over voltage fault
The UPS transfers to Bypass
mode if supporting the load
Inv Under Voltage
Alarm Code:33
Indicates that the UPS get
inverter under voltage
fault
The UPS transfers to Bypass
mode if supporting the load
Inv Softstart Fail
Alarm Code:34
Indicates that the inverter
could not soft start
successfully
Contact your service
representative
Charger Fail
Alarm Code:15
Indicates that the UPS
has confirmed the charger
has failed
The UPS turns off the
charger until the next power
recycle. Contact your service
representative
Battery Over
Voltage
Alarm Code:16
Indicates that the battery
voltage is too high
The UPS will turn off the
charger until the battery
voltage is normal
Fatal eeprom Fault
Alarm Code:A3
Indicates that the UPS
could not read eeprom
successfully
Contact your service
representative
Negative power
Fault
Alarm Code:
E1
In parallel system
,
power
of UPS is negative
Redundancy mode
,
the fault
UPS turn to fault mode
without output
Increase mode
,
UPS1&
Содержание B500-R060-C
Страница 1: ...B500 Online UPS User Manual B500 R060 C B500 R100 C 208 220 230 240VAC ...
Страница 2: ......
Страница 29: ...25 Fig 4 9 Parallel systerm wiring diagram of B500 R060 C ...
Страница 30: ...26 Fig 4 10 Parallel systerm wiring diagram of B500 R100 C ...
Страница 31: ...27 Fig 4 11 Parallel System Installation Diagram ...
Страница 43: ...39 Fig 5 14 Main menu tree ...
Страница 50: ...46 ...
Страница 51: ...47 Fig 5 19 Setting menu tree Example set rated output voltage value Fig 5 20 Set rated output voltage value ...