Battery mode:
When the UPS is running in battery mode, the
buzzer beeps once every 4 seconds.
Fig. 5.5
Bypass with output:
The UPS does not have the backup function
when it is in bypass mode. The power used
by the load is supplied from the utility power
via internal filter. The UPS will beep once
every 2 minutes in bypass mode.
Fig. 5.6
Bypass without output:
The UPS in bypass mode without output
Fig. 5.7
High Efficiency Mode:
After the UPS is turned on, the power used by
the load is supplied from the utility power via
internal filter while the utility power is in
normal range, so the high efficiency could be
gained in the HE mode. Once the mains is
loss or abnormal, the UPS would transfer to
Line mode or Battery mode and the load is
supplied continuously.
1)
The function could be enabled through
the LCD setting or the software
(Winpower, etc.).
2)
The transfer time of UPS output from
HE mode to battery mode is about
10ms. But it is still too long for some
sensitive load.