User’s Manual
49
Esr
=
8 ∗ 0.01Ω
1
= 0.08Ω
The total extraction losses of the string is given by
J
= Esr
∗ I
∗ T
J
= 0.08Ω ∗ 235A ∗ 2s = 9kJ
Now the total required energy can be compared.
J
+ J
< J
150kJ + 9kJ < 175𝑘𝐽
This combination of capacitors will be adequate for our example application.
If the application required more energy, then capacitors can be added in series,
and the calculations redone. If the charge voltage exceeds the maximum input
voltage for the M3534R, then the minimum series string combination should be
used in parallel and the process repeated.
7.3. D
IODE
S
HARING WITH A
B
ONITRON
M3534
R
IDE
-T
HRU
Diode sharing is used to decrease the cost of implementing M3534 modules to existing
drive systems that are not common bussed. The use of diodes will prevent drive
busses from “back feeding” each other, by allowing energy to pass one way only.
For Ride-Thru applications, the energy is allowed to pass from the M3534 to the drives,
but is blocked from the drives to the M3534. Figure 7-1 is a block diagram of a diode
sharing example.
Below are some basic guidelines for using diodes in this manner for M3534
applications.
9.
Drives should have equivalent DC bus levels as would be found on equal size
drives of a common manufacturer.
10.
Drives should be on same AC feed and grounding. There must be no isolation
transformers between the drives and or M3534 modules. Different feeds may
have different potentials and may cause circulating currents or ground faults.
11.
If line chokes or harmonic filters are used, all the drives should be connected
to the output of a single choke or filter. Individual input harmonic filters or line
chokes can cause unequal potentials with respect to earth.
12.
The 3534 connection should be downstream of any input line filter. Input line
filters cause lower DC bus levels. If a M3534 is placed upstream, the Ride-
Thru DC bus can be higher than the drive bus, and current can flow through
the M3534. This can cause constant activity and overheating. It may be
necessary to lower the threshold for these applications.
13.
Ground Fault sensing should be done upstream at common point of line
connection, upstream of line filter, if used.
Содержание M3534-I3
Страница 6: ...M3534 6 This page intentionally left blank ...
Страница 18: ...M3534 18 3 5 TYPICAL CONFIGURATIONS Figure 3 2 M3534R without Energy Storage ...
Страница 19: ...User s Manual 19 Figure 3 3 M3534R with Electrolytic Capacitor Storage Bank ...
Страница 21: ...User s Manual 21 Figure 3 5 M3534B 40A with Battery Storage Bank ...
Страница 22: ...M3534 22 This page intentionally left blank ...
Страница 25: ...User s Manual 25 Figure 4 2 3534I3 I O Diagram ...
Страница 40: ...M3534 40 6 5 DIMENSIONS AND MECHANICAL DRAWINGS Figure 6 1 M3534 A5 Chassis Dimensional Outline ...
Страница 41: ...User s Manual 41 Figure 6 2 M3534 K7 Chassis Dimensional Outline ...
Страница 42: ...M3534 42 Figure 6 3 M3534 K9 Chassis Dimensional Outline ...
Страница 43: ...User s Manual 43 Figure 6 4 M3534 A9 Chassis Dimensional Outline ...
Страница 51: ...User s Manual 51 NOTES ...
Страница 52: ...M3534 52 ...
Страница 53: ...User s Manual 53 ...
Страница 54: ...M3534 54 ...
Страница 55: ......