4.4.1. I
NPUT
T
ERMINALS
–
3534I3
TB4
&
TB5
The input terminals are located on TB4 & TB5 of the 3534I3 board. They can
use an internal supply with a dry contact or an external 24VDC.
4.4.1.1.
E
NABLE
I
NPUT
–
TB4
-
5
&
6
The Enable input is used to allow the M3534 to operate. This signal can
be configured for either enable or disable operation.
This input operation is configured with jumper J3 on the 3534I3 board.
The input operation is set to “Enable” with J3 set to "NC", and the M3534
will operate when 24VDC is applied to the input.
The input operation is set to “Disable” with J3 set to "NO", and the M3534
will be inhibited and not operate when 24VDC is applied to the input.
Connect the 24V positive to TB4-6 and the 24V common to TB4-5 to
enable or disable the M3534.
The isolated 15V available at TB5-9 & 10 may be used to drive this input.
The factory default setting is to have the operation set to "Enable".
Table 4-1: 3534I3 Enable Input Logic Jumper Details
J
UMPER
P
OSITION
F
UNCTION
3534I3
F
IELD
T
ERMINALS
F
ACTORY
S
ETTING
J3
NC
Enable
TB4 - 5 & 6
NC (Enable)
NO
Disable
CAUTION!
T
HE
M3534
MAY NOT OPERATE CORRECTLY IF THE UNIT IS NOT PROPERLY
CONFIGURED
.
P
AY SPECIAL ATTENTION TO THIS CONFIGURATION
,
AS THIS
CAN CAUSE THE UNIT TO NOT PROTECT THE DRIVE IN THE CASE OF A POWER
SAG OR OUTAGE
.
4.4.1.2.
T
EST
I
NPUT
–
TB5
–
6
&
10
The Test input is used to make the M3534 go into Test mode.
Connect the internal supply 15V positive at TB5–10 to the test input at
TB 5–6 to go into Test mode.
When the DP10 display is used, pressing the test button on the display
will put the M3534 into Test mode.
4.4.2. O
UTPUT
T
ERMINALS
–
3534I3
TB5
&
TB4
The status of the M3534 can be monitored from TB5 and TB4 on the 3534I3
board. The Overtemperature and Ride-Thru Active status outputs can be
configured with jumpers to be normally open (NO) or normally closed (NC).
The Ride-Thru Ready status output is hard-wired and is not jumper selectable
at TB5-4. The Ride-Thru ready status output can be configured with jumper to
normally open (NO) or normally closed (NC) at TB4-3 & 4. In the descriptions
below, the operation is described for the jumpers to be set in the normally open
position.
4.4.2.1.
O
VERTEMPERATURE
-
TB5
-
3
This output is pulled to the internal supply common when the temperature
of the heatsink remains at a safe level. The contact will open when the
temperature rises to an unsafe level. This overtemperature condition will
Содержание M3534-I3
Страница 6: ...M3534 6 This page intentionally left blank ...
Страница 18: ...M3534 18 3 5 TYPICAL CONFIGURATIONS Figure 3 2 M3534R without Energy Storage ...
Страница 19: ...User s Manual 19 Figure 3 3 M3534R with Electrolytic Capacitor Storage Bank ...
Страница 21: ...User s Manual 21 Figure 3 5 M3534B 40A with Battery Storage Bank ...
Страница 22: ...M3534 22 This page intentionally left blank ...
Страница 25: ...User s Manual 25 Figure 4 2 3534I3 I O Diagram ...
Страница 40: ...M3534 40 6 5 DIMENSIONS AND MECHANICAL DRAWINGS Figure 6 1 M3534 A5 Chassis Dimensional Outline ...
Страница 41: ...User s Manual 41 Figure 6 2 M3534 K7 Chassis Dimensional Outline ...
Страница 42: ...M3534 42 Figure 6 3 M3534 K9 Chassis Dimensional Outline ...
Страница 43: ...User s Manual 43 Figure 6 4 M3534 A9 Chassis Dimensional Outline ...
Страница 51: ...User s Manual 51 NOTES ...
Страница 52: ...M3534 52 ...
Страница 53: ...User s Manual 53 ...
Страница 54: ...M3534 54 ...
Страница 55: ......