1.
Ensure the M3534 has been properly installed and is disabled.
2.
Ensure the M3534 DC bus is disconnected from the drive DC bus.
3.
Ensure the drive is operating properly with the M3534 disconnected.
4.
Apply power to the input of the M3534 and observe the following conditions:
DC bus voltage should rise
Power light should be ON
Overtemperature light should be OFF
Ride-Thru Active light should be OFF
All status outputs are in the expected state. If there are faults on the system,
check the configuration of the status output jumpers.
5.
Enable the M3534 with either the enable input or the digital display.
6.
Initiate the test mode with the Test input or display panel.
The DC bus should rise for as long as the test is performed.
7.
Turn off the power to the M3534 and watch the DC bus voltage fall. The M3534
will become active.
The Ride-Thru Active light should turn ON when the M3534 starts to operate.
The DC bus will hold at the DC bus threshold voltage setting momentarily
while the filter capacitors drain.
8.
With the M3534 and drive power off, connect the DC bus of the M3534 to the
DC bus of the drive.
9.
Turn on power to the M3534 and the attached drive.
10.
Monitor the DC bus voltage and current with the display or with separate
meters. Also, monitor the AC input current to the attached drive.
11.
Load the drive as much as practical and put the M3534 into Test mode by
activating the Test input or using the display panel.
DC bus voltage should rise to the test boost level.
Motor should not lose speed or torque.
DC bus current should flow from M3534 to drive.
Drive input current should decrease.
The M3534 and drive system should now be ready to be put into service.
CAUTION!
I
F THE OUTPUT
DC
BUS DROPS BELOW
70%
THE
M3534
WILL HAVE TO GO THROUGH
PRE
-
CHARGE AGAIN
.
5.2. M
AINTENANCE
I
TEMS
The M3534 is designed to require no maintenance. However, Bonitron recommends
a yearly test of the system in order to ensure the system is functioning properly. If the
system is equipped with displays, then the cycle counters should indicate the number
of events since the last reset. If there are more than 10 events per month, the DC bus
threshold voltage setting should be checked and/or adjusted.
Содержание M3534-I3
Страница 6: ...M3534 6 This page intentionally left blank ...
Страница 18: ...M3534 18 3 5 TYPICAL CONFIGURATIONS Figure 3 2 M3534R without Energy Storage ...
Страница 19: ...User s Manual 19 Figure 3 3 M3534R with Electrolytic Capacitor Storage Bank ...
Страница 21: ...User s Manual 21 Figure 3 5 M3534B 40A with Battery Storage Bank ...
Страница 22: ...M3534 22 This page intentionally left blank ...
Страница 25: ...User s Manual 25 Figure 4 2 3534I3 I O Diagram ...
Страница 40: ...M3534 40 6 5 DIMENSIONS AND MECHANICAL DRAWINGS Figure 6 1 M3534 A5 Chassis Dimensional Outline ...
Страница 41: ...User s Manual 41 Figure 6 2 M3534 K7 Chassis Dimensional Outline ...
Страница 42: ...M3534 42 Figure 6 3 M3534 K9 Chassis Dimensional Outline ...
Страница 43: ...User s Manual 43 Figure 6 4 M3534 A9 Chassis Dimensional Outline ...
Страница 51: ...User s Manual 51 NOTES ...
Страница 52: ...M3534 52 ...
Страница 53: ...User s Manual 53 ...
Страница 54: ...M3534 54 ...
Страница 55: ......