M3534R 40&85A
44
7.4.3.
P
EAK
C
URRENT
The peak current from the capacitor bank will occur at the minimum voltage.
This can be estimated from the equation
I
peak
=
P
sys
V
end
For our example,
I
peak
=
75kW
320Vdc
= 235A
7.4.4.
C
APACITOR
S
PECIFICATIONS
At this point, a specific capacitor's characteristics can be used. It is best to
use the values that are listed at end of life for the capacitor to make sure that
the storage system is sized for the eventual degradation of performance over
time. The critical points to use are
𝐸𝑠𝑟
=
Internal resistance at end of life, typically 150-200% of the initial
value.
𝐶
𝑒𝑜𝑙
=
Capacitance at end of life
𝑉
𝐶𝑎𝑝𝑀𝑎𝑥
=
Maximum charge voltage for the capacitor. (A general rule is to
use
95% of the value listed on the datasheet for a reasonable margin)
For our example, we will use the following values:
𝐸𝑠𝑟
=
.01Ω
𝐶
𝑒𝑜𝑙
=
132F
𝑉
𝐶𝑎𝑝𝑀𝑎𝑥
= 46V
7.4.5.
M
INIMUM
S
ERIES
S
TRING
From
𝑉
𝑐𝑎𝑝𝑀𝑎𝑥
, we can calculate the minimum series string of capacitors that
will be required by the voltage rating. Below this voltage, there is an amount
of stored energy that cannot be used, and will remain in the capacitor bank.
Since there can be significant terminal voltage drop at the end of the
discharge cycle due to
𝐸𝑠𝑟
, it is best to use the terminal voltage of the
capacitors (
𝑉
𝑇𝑒𝑟𝑚𝐸𝑛𝑑
)
for this calculation.
V
TermEnd
= V
CapMax
− (I
peak
∗ Esr)
V
TermEnd
= 46V − (235A ∗ 0.01Ω) = 43.7V
For our example, the minimum number of caps in a series string would be:
n
series
=
V
end
V
TermEnd
=
320V
43.7V
= 8
Содержание Legacy M3534R-RY
Страница 6: ...M3534R 40 85A vi This page intentionally left blank ...
Страница 22: ...M3534R 40 85A 16 This page intentionally left blank ...
Страница 42: ...M3534R 40 85A 36 Figure 6 2 M3534R 50kW A9 Chassis Dimensional Outline Dwg 120220 Rev 20120626 ...
Страница 46: ...M3534R 40 85A 40 This page intentionally left blank ...
Страница 54: ...M3534R 40 85A 48 NOTES ...
Страница 55: ......