M3534R 40&85A
8
3.4. W
IRING AND
C
USTOMER
C
ONNECTIONS
This section provides information pertaining to the field wiring connections of the
M3534R Ride-Thru Module. Actual connection points and terminal numbers of the AC
Drive system will be found in the documentation provided with that system.
Be sure to review all pertinent AC Drive System documentation as well as the
RTM to
Drive Interconnection
details listed below before proceeding.
DANGER!
Interconnect wiring of this product should only be done by a qualified
electrician in accordance with National Electrical Code or local codes and
regulations.
Table 3-1: 40 Amp Field Power Wiring Connections
T
ERMINAL
F
UNCTION
W
IRING
S
PECIFICATIONS
M
IN
W
IRE
AWG
M
AX
W
IRE
AWG
T
ORQUE
LB
-
IN
L1 L2 L3
AC Input
600
VAC
14
10
20 lb-in
Storage Bus
+
─
DC Input
600VAC
12
4
32 lb-in
DC Bus
+
─
DC Output
600
VAC
14
10
20 lb-in
GND
Ground
600
VAC
18
10
20 lb-in
Table 3-2: 85 Amp Field Power Wiring Connections
T
ERMINAL
F
UNCTION
W
IRING
S
PECIFICATIONS
M
IN
W
IRE
AWG
M
AX
W
IRE
AWG
T
ORQUE
LB
-
IN
L1 L2 L3)
AC Input
600
VAC
12
4
32 lb-in
Storage Bus
+
─
DC Input
600VAC
12
4
32 lb-in
DC Bus
+
─
DC Output
600
VAC
12
4
32 lb-in
GND
Ground
600
VAC
18
10
20 lb-in
3.4.1. P
OWER
W
IRING
-
RTM
T
O
D
RIVE
I
NTERCONNECTIONS
Illustrations and a table are provided to assist with the field connection of the
M3534R Ride-Thru Module to an existing AC drive system. Also, be sure to
refer to the documentation supplied with the drive system for field connection
points within that system. The DC bus should always be connected directly
to the drive output capacitor bank. Connecting upstream of the DC bus
inductors may cause damage to the drive and Ride-Thru module.
Typical Field Connection terminal layouts for the M3534R RTM are shown in
Figures 3-1 through 3-5. Figure 3-6 shows a typical power interconnection of
the M3534R Ride-Thru Module with an existing AC drive system.
Field connection terminals for the Ground, AC Line Input, External Energy
Reservoir, and DC Bus are located near the bottom of the RTM enclosure
and can be accessed by removing the cover panel from the enclosure. For
additional terminal identification, please refer to the appropriate chassis
Содержание Legacy M3534R-RY
Страница 6: ...M3534R 40 85A vi This page intentionally left blank ...
Страница 22: ...M3534R 40 85A 16 This page intentionally left blank ...
Страница 42: ...M3534R 40 85A 36 Figure 6 2 M3534R 50kW A9 Chassis Dimensional Outline Dwg 120220 Rev 20120626 ...
Страница 46: ...M3534R 40 85A 40 This page intentionally left blank ...
Страница 54: ...M3534R 40 85A 48 NOTES ...
Страница 55: ......