USING
The following data is supplied for assistance in selecting the appropriate field
wiring sizes and power source fuse ratings for the model M3534R Cabinet
Mounted and Open-chassis Ride-Thru systems.
Wire size must be coordinated with circuit protection devices and IR drop
of wire. It is NOT necessary to size wire for continuous duty. Maximum
allowed duty cycle for the M3534R Ride-Thru is one 2-second run every 4
minutes.
Table 6-3: Input Power Wiring Sizes and Fusing
S
YSTEM
K
W
R
IDE
-T
HRU
DC
B
US
C
URRENT
R
ATING
M
IN
.
S
OURCE
F
USING
S
EMICONDUCTOR
R
ECOMMENDED
F
IELD
W
IRING
S
IZES
MCM
E
QUIVALENT
W
IRING
S
IZES
20 - 24
40 Amps
60 Amps
8 - 10 AWG
16 MCM
43 - 50
85 Amps
125 Amps
4 - 6 AWG
41 MCM