M3534R 40&85A
10
3.4.2. C
ONTROL
I
NTERFACE
W
IRING
3.4.2.1. T
EST
I
NPUT
C
ONNECTIONS
40 and 85 Amp units:
Test input connections may be made across
TB6-
1
(Positive) and
TB6-2
(Negative) of the ASB 3534R3 Control Board.
Torque terminal screws to 2 lb-in max.
3.4.2.2. D
ISABLE
I
NPUT
C
ONNECTION
The Disable Input connections are made directly to the DISABLE relay at
the top of the module. Use .20” female spade lugs. See Figures 3-3 and
3-4. If DP10 option is installed (I3 board), the Disable Input is at TB4-5(-
) & 6(+).
3.4.2.3. F
AULT
/
S
TATUS
M
ONITORING
C
ONNECTIONS FOR
S
TANDARD
M
ODELS
40 and 85 Amp units
: On the ASB 3534R3 Control Board:
See Figures 3-3 and 3-4.
To monitor the OVERTEMP Fault Relay connect across
TB5-2
(OT) and
TB5-4
(Common).
To monitor the RIDE-THRU ACTIVE Relay connect across
TB5-3
(RTA)
and
TB5-4
(Common).
3.4.2.4. F
AULT
/
S
TATUS
M
ONITORING
C
ONNECTIONS FOR
M
ODELS WITH
DP10
(3534I3
B
OARD
)
Ride-Thru Active (RTA) Relay
: On the ASB 3534I3 Interface Board:
TB4-1
(J2 post) and
TB4-2
(common).
Ride-Thru Ready (RTR) Relay
: On the ASB 3534I3 Interface Board:
TB4-3
(J1 post) and
TB4-4
(common).
Содержание Legacy M3534R-RY
Страница 6: ...M3534R 40 85A vi This page intentionally left blank ...
Страница 22: ...M3534R 40 85A 16 This page intentionally left blank ...
Страница 42: ...M3534R 40 85A 36 Figure 6 2 M3534R 50kW A9 Chassis Dimensional Outline Dwg 120220 Rev 20120626 ...
Страница 46: ...M3534R 40 85A 40 This page intentionally left blank ...
Страница 54: ...M3534R 40 85A 48 NOTES ...
Страница 55: ......