4.1.3

 

Characteristic 

 

The mapping of the analog input signals onto a frequency or percentage reference 

value is possible for various demands. The parameterization is to be done via two

points of the linear characteristic of the reference channel. 

The characteristic point 1, with the coordinates X1 and Y1, and the characteristic point

2, with the coordinates X2 and Y2, can be set in four parameters. 

The characteristic points X1 and X2 are stated as percentages, as the analog input can
be switched as a current or voltage input via switch S3. 

 

Parameter 

Setting 

 

No. Description 

Min. 

Max. 

Fact. 

sett. 

 

564  Characteristic point X1 

-100.00 %  100.00 % 

-98.00 % 

 

565  Characteristic point Y1 

-100.00 %  100.00 %  -100.00 % 

 

566  Characteristic point X2 

-100.00 %  100.00 % 

98.00 % 

 

567  Characteristic point Y2 

-100.00 %  100.00 % 

100.00 % 

 

The coordinates of the characteristic points are related as a percentage to the analog
signal, with 10 V or 20 mA, and the parameter 

Maximum Frequency

 419 or parame-

ter 

Maximum reference percentage

 519. The change of direction of rotation can be 

done via the digital inputs of the frequency inverter and/or by selecting the character-

istic points. 

 

The definition of the analog input characteristic can be calculated via the two-point 

form of the straight-line equation. The speed Y of the drive mechanism is controlled

according to the analog control signal X. 

 

(

)

Y1

X1

X

X1

-

X2

Y1

-

Y2

 

Y

+

=

 

 

Attention! Monitoring of the analog input signal via the parameter 

Error/Warning

Behavior

 563 demands a check of the characteristic parameters. Sensible

use is only possible if the 

Characteristic point X1

 564 is in the positive

range. 

 

4.1.4

 

Operation modes 

 

The operation modes of the analog input characteristic enable application-related scal-

ing as a supplement to the characteristic points stated. One of the four linear types of

characteristic is selected for adaptation of the signal for the analog input signal via the
parameter 

Operation mode

 562

If the characteristic points are not suited for the type of characteristic selected, the
characteristic points are corrected internally. 

 

Operation mode 

Function 

 

1 - bipolar 

The analog input signal is mapped onto the reference 
figure according to the characteristic points (X1/Y1) 

and (X2/Y2). 

 

11 - unipolar 

With a negative parameter value of the characteristic 

points X1 or X2, they are mapped to the reference 
value zero. 

 21 

unipolar 

2…10 V / 4…20 mA 

If the characteristic points X1 or X2 have been set 

with a negative parameter figure or smaller than 0%, 
the input characteristic is mapped to the reference 

value 20%. 

 

101 - bipolar absolute value  Negative parameter values of the characteristic points 

Y1 or Y2 are mapped as a positive reference value in 

the characteristic. 

 

Further information on the operation modes stated in the table can be found in the 

following chapter "Examples“. 

 

Содержание EM-RES-02

Страница 1: ...AND UTOMATION OLUTIONS A S I P NDUSTRY ROCESS ACTIVE and ACTIVE Cube Expansion Module EM RES 02 GB Frequency Inverter 230 V 400 V...

Страница 2: ...uctions describe the mechanical installation and use of devices which differ from those described in the brief instructions and the operating instruc tions The documentation and additional information...

Страница 3: ...ets 9 4 Control inputs and outputs 10 4 1 Analog input EM S1INA 10 4 1 1 General 10 4 1 2 Configuration voltage current input 10 4 1 3 Characteristic 11 4 1 4 Operation modes 11 4 1 4 1 Examples 12 4...

Страница 4: ...vers improper use wrong installation or operation there is the risk of serious damage to persons or property To avoid the damage only qualified staff may carry out the transport installation setup or...

Страница 5: ...rter is de energized Do not touch the sockets because the capacitors may still be charged Comply with the information given in the operating instructions and on the frequency inverter label While work...

Страница 6: ...nsion module is supported from device series ACU and as from software version 4 1 0 of device series ACT The EM RES 02 module extends the functionality of the frequency inverters of the ACT and ACU de...

Страница 7: ...urther information refer to the operating instructions of the frequency inverter Danger All connection sockets where dangerous voltage levels may be present e g motor connection sockets mains sockets...

Страница 8: ...module becomes accessible 1 Caution The EM RES 02 expansion module 2 is pre fitted in a housing Do NOT touch the PCB visible on the back as modules may be damaged Plug the EM RES 02 expansion module 2...

Страница 9: ...been discharged 3 3 1 Circuit diagram 6 X410A X410B 5 6 7 5 EM RFOUT B EM RFOUT A 7 3 1 2 4 B B C EM S1INA A D GND EM RFOUT R EM RFOUT R EM RFOUT B EM RES SIN 4 EM RES REF EM RES REF 3 1 2 EM RES SIN...

Страница 10: ...field signal lines cable for connecting the resolver The line screen is to be connected to PE on a plane at both ends Socket X410A Ter Description 1 Resolver field signal EM RES REF 2 Resolver field...

Страница 11: ...age source 476 actual percentage source can be selected via the parameter Actual percentage source 478 in configura tion x11 or limit value sources can be selected via the parameters 734 737 4 1 2 Con...

Страница 12: ...s controlled according to the analog control signal X Y1 X1 X X1 X2 Y1 Y2 Y Attention Monitoring of the analog input signal via the parameter Error Warning Behavior 563 demands a check of the characte...

Страница 13: ...teristic points Characteristic point 1 X1 70 00 10 V 7 00 V Y1 50 00 50 00 Hz 25 00 Hz Characteristic point 2 X2 80 00 10 V 8 00 V Y2 85 00 50 00 Hz 42 50 Hz Tolerance band X 2 00 10 V 0 20 V X2 80 Y2...

Страница 14: ...0 X value parameter X point stic characteri Characteristic point 1 X1 70 00 100 00 20 00 20 00 10 V 7 60 V Y1 50 00 50 00 Hz 25 00 Hz Characteristic point 2 X2 80 00 100 00 20 00 20 00 10 V 8 40 V Y2...

Страница 15: ...input signal is mapped to the freely configurable characteristic The maxi mum admissible setting range of the drive mechanism is to be set according to the configuration selected via the frequency lim...

Страница 16: ...10V 20mA 10V 20mA X2 Y2 pos max value neg max value Without tolerance band X1 Y1 10V 20mA 10V X2 Y2 pos max value Tolerance band neg max value With tolerance band The Minimum Frequency 418 or the Min...

Страница 17: ...stops freely The monitoring of the analog input signal is active independent of the release of the frequency inverter according to the operation mode selected In operation mode 2 the drive mechanism...

Страница 18: ...ink from the socket of the ana log input to socket X210B 5 reference output 10 V of the frequency inverter Select operation mode 2 Adjustment 10 V 20 mA 4 1 9 Filter time constant The time constant of...

Страница 19: ...ES X410A 6 COS 4 2 1 Offset In order to enable the start of a synchronous machine the absolute position of the rotor must be known This information is required in order to actuate the stator wind ings...

Страница 20: ...at there are no excessive currents of the offset is set incorrectly Turn motor shaft manually Check the sense of rotation of the resolver via the ac tual value of parameter Frequency Speed Sensor 2 21...

Страница 21: ...eference value and start the motor If the motor does not start despite the phase exchange Increase the parameter value for Offset 382 by 90 divided by the no of mo tor pole pairs If the motor still do...

Страница 22: ...connection of the available reference sources as a function of the installed hardware Operation mode Function 2 EM S1INA absolute value Reference source is the analog input EM S1INA 4 MFI1A EM S1INA...

Страница 23: ...RFOUT emulates a speed sensor The repetition frequency output delivers the frequency signal of the resolver as a simulation of an incremental speed sensor with reference signal The number of division...

Страница 24: ...sor 2 Hz 0 0 999 99 4 4 220 Speed speed sensor 2 rpm 0 60000 4 4 Actual values of the frequency inverter 253 Analog input EM S1INA 100 100 4 4 5 2 Parameter menu PARA Resolver No Description Unit Sett...

Страница 25: ...lver signal for inter ferences 22 Resolver counting error Check resolver signal for interferences 23 Resolver pole pair number is invalid The ratio of the no of pole pairs to the no of resolver pole p...

Страница 26: ...r kb lint T u 2 Hungary Tel 36 23 50 11 50 Fax 36 23 50 11 59 www agisys hu info agisys com INDIA BONFIGLIOLI TRANSMISSIONS PVT Ltd PLOT AC7 AC11 Sidco Industrial Estate Thirumudivakkam Chennai 600 04...

Страница 27: ...w w w b o n f i g l i o l i c o m I P NDUSTRY ROCESS AND UTOMATION OLUTIONS A S ACTIVE and ACTIVE Cube COD VEC 225 R2...

Отзывы: