background image

 

 

 

 

08/06 

 

13

 

Characteristic point 1: 

X1 = 30.00 % · 10 V = 3.00 V 

Y1 = -50.00 % · 50.00 Hz = -25.00 Hz

 

 

Characteristic point 2: 

X2 = 80.00 % · 10 V = 8.00 V 

Y2 = 85.00 % · 50.00 Hz = 42.50 Hz 

 

Tolerance band: 

Δ

X = 2.00 % · 10 V = 0.20 V 

 

 

(X2=80% / Y2=85%)

8.00V

Y

X

-25.00Hz

42.50Hz

(X1=30% / Y1=-50%)

3.00V

The change of direction of rotation is done 

in the example at an analog input signal of 

4.85 V, with a tolerance band of ±0.20 V. 

 

Operation mode "21 – unipolar 2…10 V / 4…20 mA" 

 

This operation mode limits the input characteristic to the range between 20% and

100% of the analog signal. If the value for a characteristic point of the X-axis is out-
side 0%, it is mapped to the characteristic point (2 V / 0 Hz). 

 

The characteristic point on the X-axis is calculated according to the following formula: 

 

20.00%

20.00%)

-

(100.00%

X

 

value

parameter 

X

point 

 

stic

characteri

+

=

 

Characteristic point 1: 

X1 = [-70.00% · (100.00% - 20.00%)  

+ 20.00% ] · 10 V = -7.60 V 

Y1 = -50.00% · 50.00 Hz = -25.00 Hz

 

 

Characteristic point 2: 
X2 = [80.00% · (100.00% - 20.00%)  

+ 20.00% ] · 10 V = 8.40 V 

Y2 = 85.00% · 50.00 Hz = 42.50 Hz 

 

Tolerance band: 

Δ

X = [2.00% · (100.00% - 20.00%) 

 · 10 V] = 0.16 V 

 

 

(X2=80% / Y2=85%)

8.40V

Y

X

-25.00Hz

42.50Hz

(X1=-70% / Y1=-50%)

-7.60V

The characteristic point 1 has been dis-

placed to the point (2.00 V / 0.00 Hz). The 
parameter 

Tolerance band

  560 is not 

used in this example, as no change of sign 

of the reference frequency value takes 

place. 
Characteristic point 1: 
X1 = [30.00% · (100.00% - 20.00%)  

+ 20.00% ] · 10 V = 4.40 V 

Y1 = -50.00% · 50.00 Hz = -25.00 Hz

 

 

Characteristic point 2: 
X2 = [80.00% · (100.00% - 20.00%)  

+ 20.00% ] · 10 V = 8.40 V 

Y2 = 85.00% · 50.00 Hz = 42.50 Hz 

 

Tolerance band: 

Δ

X = [2.00% · (100.00% - 20.00%) 

 · 10 V] = 0.16 V 

 

 

(X2=80% / Y2=85%)

8.40V

Y

X

-25.00Hz

42.50Hz

(X1=30% / Y1=-50%)

4.40V

The change of direction of rotation is done 

in the example at an analog input signal of 

5.88 V, with a tolerance band of ±0.16 V. 

Содержание EM-RES-02

Страница 1: ...AND UTOMATION OLUTIONS A S I P NDUSTRY ROCESS ACTIVE and ACTIVE Cube Expansion Module EM RES 02 GB Frequency Inverter 230 V 400 V...

Страница 2: ...uctions describe the mechanical installation and use of devices which differ from those described in the brief instructions and the operating instruc tions The documentation and additional information...

Страница 3: ...ets 9 4 Control inputs and outputs 10 4 1 Analog input EM S1INA 10 4 1 1 General 10 4 1 2 Configuration voltage current input 10 4 1 3 Characteristic 11 4 1 4 Operation modes 11 4 1 4 1 Examples 12 4...

Страница 4: ...vers improper use wrong installation or operation there is the risk of serious damage to persons or property To avoid the damage only qualified staff may carry out the transport installation setup or...

Страница 5: ...rter is de energized Do not touch the sockets because the capacitors may still be charged Comply with the information given in the operating instructions and on the frequency inverter label While work...

Страница 6: ...nsion module is supported from device series ACU and as from software version 4 1 0 of device series ACT The EM RES 02 module extends the functionality of the frequency inverters of the ACT and ACU de...

Страница 7: ...urther information refer to the operating instructions of the frequency inverter Danger All connection sockets where dangerous voltage levels may be present e g motor connection sockets mains sockets...

Страница 8: ...module becomes accessible 1 Caution The EM RES 02 expansion module 2 is pre fitted in a housing Do NOT touch the PCB visible on the back as modules may be damaged Plug the EM RES 02 expansion module 2...

Страница 9: ...been discharged 3 3 1 Circuit diagram 6 X410A X410B 5 6 7 5 EM RFOUT B EM RFOUT A 7 3 1 2 4 B B C EM S1INA A D GND EM RFOUT R EM RFOUT R EM RFOUT B EM RES SIN 4 EM RES REF EM RES REF 3 1 2 EM RES SIN...

Страница 10: ...field signal lines cable for connecting the resolver The line screen is to be connected to PE on a plane at both ends Socket X410A Ter Description 1 Resolver field signal EM RES REF 2 Resolver field...

Страница 11: ...age source 476 actual percentage source can be selected via the parameter Actual percentage source 478 in configura tion x11 or limit value sources can be selected via the parameters 734 737 4 1 2 Con...

Страница 12: ...s controlled according to the analog control signal X Y1 X1 X X1 X2 Y1 Y2 Y Attention Monitoring of the analog input signal via the parameter Error Warning Behavior 563 demands a check of the characte...

Страница 13: ...teristic points Characteristic point 1 X1 70 00 10 V 7 00 V Y1 50 00 50 00 Hz 25 00 Hz Characteristic point 2 X2 80 00 10 V 8 00 V Y2 85 00 50 00 Hz 42 50 Hz Tolerance band X 2 00 10 V 0 20 V X2 80 Y2...

Страница 14: ...0 X value parameter X point stic characteri Characteristic point 1 X1 70 00 100 00 20 00 20 00 10 V 7 60 V Y1 50 00 50 00 Hz 25 00 Hz Characteristic point 2 X2 80 00 100 00 20 00 20 00 10 V 8 40 V Y2...

Страница 15: ...input signal is mapped to the freely configurable characteristic The maxi mum admissible setting range of the drive mechanism is to be set according to the configuration selected via the frequency lim...

Страница 16: ...10V 20mA 10V 20mA X2 Y2 pos max value neg max value Without tolerance band X1 Y1 10V 20mA 10V X2 Y2 pos max value Tolerance band neg max value With tolerance band The Minimum Frequency 418 or the Min...

Страница 17: ...stops freely The monitoring of the analog input signal is active independent of the release of the frequency inverter according to the operation mode selected In operation mode 2 the drive mechanism...

Страница 18: ...ink from the socket of the ana log input to socket X210B 5 reference output 10 V of the frequency inverter Select operation mode 2 Adjustment 10 V 20 mA 4 1 9 Filter time constant The time constant of...

Страница 19: ...ES X410A 6 COS 4 2 1 Offset In order to enable the start of a synchronous machine the absolute position of the rotor must be known This information is required in order to actuate the stator wind ings...

Страница 20: ...at there are no excessive currents of the offset is set incorrectly Turn motor shaft manually Check the sense of rotation of the resolver via the ac tual value of parameter Frequency Speed Sensor 2 21...

Страница 21: ...eference value and start the motor If the motor does not start despite the phase exchange Increase the parameter value for Offset 382 by 90 divided by the no of mo tor pole pairs If the motor still do...

Страница 22: ...connection of the available reference sources as a function of the installed hardware Operation mode Function 2 EM S1INA absolute value Reference source is the analog input EM S1INA 4 MFI1A EM S1INA...

Страница 23: ...RFOUT emulates a speed sensor The repetition frequency output delivers the frequency signal of the resolver as a simulation of an incremental speed sensor with reference signal The number of division...

Страница 24: ...sor 2 Hz 0 0 999 99 4 4 220 Speed speed sensor 2 rpm 0 60000 4 4 Actual values of the frequency inverter 253 Analog input EM S1INA 100 100 4 4 5 2 Parameter menu PARA Resolver No Description Unit Sett...

Страница 25: ...lver signal for inter ferences 22 Resolver counting error Check resolver signal for interferences 23 Resolver pole pair number is invalid The ratio of the no of pole pairs to the no of resolver pole p...

Страница 26: ...r kb lint T u 2 Hungary Tel 36 23 50 11 50 Fax 36 23 50 11 59 www agisys hu info agisys com INDIA BONFIGLIOLI TRANSMISSIONS PVT Ltd PLOT AC7 AC11 Sidco Industrial Estate Thirumudivakkam Chennai 600 04...

Страница 27: ...w w w b o n f i g l i o l i c o m I P NDUSTRY ROCESS AND UTOMATION OLUTIONS A S ACTIVE and ACTIVE Cube COD VEC 225 R2...

Отзывы: