5
Parameter
Description
Value
Range
Factory Value
3. On/Off
Events
Enables (disables) transmit-
ting events about relay’s
having activated/inactivated
On/Off
relay 1
relay 2
relay 3
relay 4
Off
Off
Off
Off
4. Both Power
Inputs
Monitoring
Provides monitoring power
voltage at both power inputs
On/Off
Off
5. Network
Address
The unique number of the
module within the RS-485
interface bus
1…127
127
1.4.6.1 The
Initial Condition
parameter of each relay defines the condition of the relay
just after powering on the module until a control command has been received from the
network controller for the relay. The values 9 (Lamp) and 10 (Alarm Output) of this parameter
are special ones.
If
Initial Condition
is equal to 9 (Lamp) then upon module’s powering on the relay
switches on, but in case of losing communication with the network controller over the RS-485
interface for a time exceeding
Activation Time
, the relay will be switched off and on once per
second. When the communication is restored, the relay will be switched on again.
If
Initial Condition
is equal to 10 (Alarm Output) then upon powering on the module this
relay will be activated but in case of breaking communication with the network controller over
the RS-485 interface bus for a time more than the parameter
Activation Time
, the relay will
be switched off. When the communication is restored, the relay will be switched on again.
1.4.6.2 For each relay, its parameter
Activation Time
defines the time for which the
relay will be activated (switched off) upon module’s receiving a Switch On for a Time or
Switch Off for a Time command in case when the activation time is not explicitly given in the
received command (provided that the module operates under a console S2000 of a version
less than 1.20). If the module S2000-SP1 mod.01 operates under an S2000 console of a
version 1.20+ or Orion Pro software, the activation time is defined during configuring the
S2000 or programming Orion Pro database, with values of the relevant parameters of the
S2000-SP1 mod.01 module being ignored.
1.4.6.3 The parameter
On/Off Events
can also be programmed for each relay
individually. If the parameter is set up (marked by “+”) then upon activating (by any way) or
inactivating the relay its new status - On (active) or Off (inactive) - will be sent over the RS-
485 interface bus as an event. In case of communication loss this event is stored in the
module non-volatile memory until restoring the failure. (Before setting this parameter, please
be sure that it is supported by the network controller being in use).
1.4.6.4 The parameter
Both Power Input Monitoring
controls the function of monitoring
power at both inputs automatically (see Clause 1.4.4.1).
1.4.6.5 To change module’s configuration parameters, an S2000(M) console or IBM
compatible PC is used. When using the PC, the configuration parameters are given by means
of
UProg
Configuration Tool, with the module being connected to a COM port of the PC
through one of the RS-232/RS-485 interface converters PI-GR and S2000-PI or an S2000(M)
console of version 1.20+ switched to the interface converter mode.