Maintenance
5.2
General
Page 34
BOGE Operating instructions for C 10 L...C 20 L series screw compressors
Maintenance work
Maintenance intervals in operating hours
1
)
Page
weeky,
monthly
1,000
annually
1,500
annually
3,000
annually
9,000
every
2 years
General maintenance work
Check final compression temperature
(set point value: 158...212°F)
w
Control
Check compressor for leaks
X
–
Check system relief on system pressure gauge (22)
(set point value: 0...22 psig)
w
Control
Check function of EMERGENCY STOP button
m
-
Clean oil cooler
X
Draining off condensate from compr. air receiver
w
–
Check automatic condensate drainage
w
–
Check if electrical connections are tightened
X
–
Air circuit
Check and if necessary clean suction filter
m
Change suction filter cartridge
X
Check safety valve
X
Replace minimum pressure valve
(wearing parts set)
X
–
Replace suction controller
X
–
Oil circuit
Check oil level and top up as required
2
)
X
Change oil separator
2)
X
Change oil filter
X
Change oil
X
Replace oil regulator (wearing parts set)
X
–
Replace nozzle with dirt catch
X
Drive
Lubricate drive motor bearings
Drive motors with permanent lubrication
Replace motor bearing
Depending on mains frequency: 50 Hz 10,000 operating hours
60 Hz 8,000 operating hours
1)
If the compressor is not often used, undertake the maintenance according to the specified intervals (weekly/monthly/annually) depending on the number of operating
hours.
2)
The specified intervals only apply when BOGE compressor oil
Syprem 8000 S
is used! The service life may differ depending on the ambient temperature. In this case
have the oil analyzed by your BOGE service!
Table 5.1: Maintenance intervals